Page 1
MODEL RCEM PORTABLE FLEXIBLE VERSION RECTIFIER MONITORING SYSTEM Installation, Operation and Service Manual Manual Item No. 043756 Rev. G DynAmp, LLC 3735 Gantz Road Phone +1 614.871.6900 www.dynamp.com Grove City, Ohio 43123 USA Fax +1 614.871.6910 help@dynamp.com...
Page 3
Items and components not manufactured and resold by Seller are warranted by their manufacturer. Warranty repair shall be, at DynAmp's option, in the form of repair or replacement of the defective items or components. Concerning warranty repairs, DynAmp will be responsible for DynAmp provided time, material and transportation costs (shipping or travel).
Page 5
Disconnect power to the system before servicing or replacing fuses. Use of the equipment in a manner not specified by the manufacturer can impair the protection provided within. DynAmp does not assume liability for the customer’s failure to comply with the GENERAL rules and requirements provided in this manual.
Page 7
Installation, Operation and Service Manual RCEM DynAmp, LLC Customer Support For further assistance, contact DynAmp Customer Support at: Americas: Telephone: +1 614.871.6900 Fax: +1 614.871.6910 8:00 AM to 5:00 PM USA Eastern Time From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT From second Sunday in March to first Sunday in November –...
The DynAmp RECTIFIER MONITORING SYSTEM Model RCEM is designed for isolated measurement of device currents in multiple path power rectifiers. Model RCEM is a monitoring system composed of a 120 Channel Data Acquisition Unit, a laptop computer, Flexible Current Sensors, and the interconnection cables.
FLEXIBLE CURRENT SENSORS The 3.625 ID Flexible Current Sensor is the standard sensor supplied with the RCEM. Other Flexible Current Sensor sizes are available from DynAmp, if required. Presently they include inside diameter (I.D.) sizes of 1.000", 1.500", 2.750", 4.250", and 2.875” x 5.500”...
Installation, Operation and Service Manual RCEM initialization sequence upon power-up. A “RCEM RESET” command from the spreadsheet program will also cause the integrator resets to synchronize to the ac line. To work properly, each integrator must be reset when the associated rectifier device is not conducting current during the commutation cycle.
Section 6 describes how to check for such paths. The Flexible Current Sensors are factory calibrated to DynAmp’s standard Flexible Current Sensor circuit. All Flexible Current Sensors are interchangeable regardless of the physical size.
Turn ON the Data Acquisition Unit using the power switch located on the I/O Panel. f.) Put the rectifier back on-line and bring it up to load. The RCEM may be tested, using its built-in test signal generator, during rectifier testing. Use the procedure in Appendix B.9 whenever the RCEM measurements indicate a problem in a rectifier, before taking the rectifier off-line.
This section contains some specialized tests of the electronics and current sensors of the RCEM, as well as some preventive maintenance procedures. The output of the built-in signal generator provides a test signal for testing the overall operation of the RCEM as well as its accuracy.
Keep plastic, vinyl, Styrofoam and other non-conductive materials away from printed circuit boards. They are good static generators that do not give up their charge easily. Return goods to DynAmp in static safe packaging. This will limit further component damage from ESD. CAUTION Do not touch any printed circuit board unless you are wearing a grounded wrist strap, as circuit damage may occur.
Make sure that all integrator cards are properly seated in the card rack. Connect the oscilloscope to the questionable waveform test points. See Figure 7.2. With the laptop computer connected to the Personal Daq/56, click on the “RCEM RESET” button on the spreadsheet.
20). SENSOR TESTING (CONTINUITY METHOD) The current sensor continuity test (described below) is made when the RCEM is first installed and will also prove useful in troubleshooting. The dielectric test, paragraph 7.9, is another useful preventive maintenance and diagnostic tool.
Replace any defective current sensor(s) and repeat the test. 7.10 SENSOR DIELECTRIC TESTING - WINDINGS TO SURFACE Dielectric withstand-voltage tests of the current sensors can be useful in preventive maintenance and troubleshooting of the RCEM. WARNING DANGER HIGH VOLTAGE exists while performing Hipot tests.
The “RCEM RESET” command button will also cause the Data Acquisition Unit to synchronize to the rectifier. This may be accomplished by turning the DAU power off then on, or by clicking on the “RCEM RESET” command button located on the laptop computer spreadsheet.
Installation, Operation and Service Manual RCEM 8. SERVICE, PARTS, AND DOCUMENTATION SERVICE ASSISTANCE For further assistance, contact DynAmp Customer Support at: Americas: Telephone: +1 614.871.6900 Fax: +1 614.871.6910 8:00 AM to 5:00 PM USA Eastern Time From first Sunday in November to second Sunday in March – 13:00 GMT to 22:00 GMT From second Sunday in March to first Sunday in November –...
Requests for spare parts, either in an emergency or for a routine order, should be directed to "Inside Sales" at DynAmp during normal hours, if possible, or via any method shown above for off-hours. When contacting us, please present as much information as possible - the related equipment Model Number and Serial Number;...
Drawings should be kept with the manual at all times. TABLE 9.1 DRAWING LIST DRAWING TITLE NUMBER Interconnection Diagram: RCEM 120 Channel COP (6-Pulse) 02D108554 Interconnection Diagram: RCEM 120 Channel COP (12-Pulse) 02D108555 Outline and Mounting: RCEM DAU 120 Channel 02D108504 Outline and Mounting: COP 3.625 ID Flexible...
RCEM APPENDIX B: SOFTWARE PROVIDED SOFTWARE All software and drivers associated with this product are supplied on CD-ROMs. The contents of the DynAmp CD-ROM are as follows: DynAmp spreadsheet(s) • Personal Daq/56 configuration file: “RCEM.cfg” • A copy of this manual “043526x.pdf” (x = manual revision) •...
The pDaqView drivers communicate with the Personal Daq/56 via the laptop’s USB port. The customized spreadsheet file(s) provided on the DynAmp CD-ROM should be copied to the “Program Files\pDaqView” directory and the “RCEM.cfg” file should be copied to the “Program Files\pDaqView\Applications” directory. Finally, a shortcut to each spreadsheet should be created on the “Desktop”...
The spreadsheet allows the monitoring of the diode currents, and provides visual indicators of all the alarm conditions. It also allows the RCEM system to be operated in test mode to assist in troubleshooting problems with the system.
20.) DEVICES/LEG: Command button used to enter the number of rectifying devices/leg. Note: This command button may not be preset on some RCEM spreadsheets. 21.) ANSI RECTIFIER CIRCUIT: Selection box used to select the appropriate ANSI Rectifier Circuit Number.
CAUTION Do not turn RCEM DAU power off when SCAN mode is active. The computer may lose communications with the RCEM DAU. See “Recovering from DAQ Errors” below to correct problem.
B.15 CALIBRATE WORKSHEET A special worksheet is provided for use in calibrating the RCEM. See Figure B.6. The diode data are displayed in rows and the legs in columns. Each row corresponds to an Integrator PC Board. The average of the diode currents in each row is calculated and displayed.