Termination clearance for buildings with combustible and noncombustible exteriors.
INSIDE CORNER
"A" = COMBUSTIBLE 9" (229mm)
= NONCOMBUSTIBLE 2" (51mm)
WITH PERPENDICULAR SIDE WALL
"G" = COMBUSTIBLE 9" (229mm)
= NONCOMBUSTIBLE 2" (51mm)
"H" = COMBUSTIBLE 18" (457mm)
= NONCOMBUSTIBLE 12" (305mm)
Vertical Sidewall Installations
Important! Minimum clearance between vent pipes and
combustible materials is 3 inch on top, and 1 inch on bottom and
sides.
Important! When vent termination exits through foundation less
than 20 inch below siding outcrop, the vent pipe must extend
outward so that the horizontal vent termination is located flush to,
or beyond the outcrop siding.
Information on Various Venting Routes and Components
Important: It is always best to locate the fireplace in such a way
that minimizes the number of offsets and horizontal vent length.
Since it is very important that the venting system maintain its
balance between the combustion air intake and the flue gas
exhaust, certain limitations as to vent configurations apply and
must be strictly adhered to. See allowed vent configurations,
page 28 to 32.
Page 14

VENT TERMINATION CLEARANCES

"F" = COMBUSTIBLE 6" (152mm)
BALCONY
OUTSIDE CORNER
= NONCOMBUSTIBLE 6" (152mm)
BALCONY
WITH NO SIDE WALL
Figure 11
The horizontal vent run refers to the total length of vent pipe from
the flue collar of the fireplace to the face of the outer wall.
Venting termination shall not be recessed into wall or siding.
ATTENTION: Vinyl Soffit, Vinyl Ceiling, Vinyl Overhang
Disclaimer
Clearances are to heat resistant material (i.e. wood, metal).
This does not include vinyl. Empire Comfort Systems Inc.
will not be held responsible for heat damage caused from
terminating under vinyl overhangs, vinyl ceilings or vinyl
ventilated/unventilated soffits.
RECESSED LOCATION
"C" = CLEARANCE FROM CORNER
IN RECESSED LOCATION
COMBUSTIBLE 9" (229mm)
NONCOMBUSTIBLE 2" (51mm)
"D" = MINIMUM WIDTH FOR BACK WALL
OF A RECESSED LOCATION
COMBUSTIBLE 38" (965mm)
NONCOMBUSTIBLE 24" (610mm)
"E" = MAXIMUM DEPTH OF 48" (1219mm)
FOR RECESSED LOCATION