Conformity to UL standards and Canadian standards (cUL certification) continued
If installed according to the guidelines given below, Drives marked with UL/cUL are considered as compliant with
the UL and CSA (cUL certified) standards.
CAUTION
1. Solid state motor overload protection (motor protection by electronic thermal overload relay) is provided in each
model.
Adjust function F10 to F12 decide the protection Level.
2. Connect the power supply satisfying the characteristics shown in the table below as an input power supply of
the drive.(Short circuit rating)
3. Use 75˚ C Cu wire only.
4. Use Class 1 wire only for control circuits.
5. Field wiring connection must be made by a UL Listed and CSA Certified closed-loop terminal connector sized
for the wire gauge involved. Connector must be fixed using the crimp tool specified by the connector manufac-
turer.
Short circuit rating
Suitable for use on a circuit capable of delivering not more than B rms symmetrical amperes, A Volts maximum.
Power supply
voltage
Drive Hp
Power supply max. voltage A
1/8
1/4
1/2
1
2
3
5
1/2
1
2
3
5
1/8
1/4
1/2
1
2
3
1/8
1/4
1/2
1
vii
Power supply current B
240 Vac
100,000 A or less
480 Vac
100,000 A or less
240 Vac
100,000 A or less
120 Vac
65,000 A or less