GE Fuji Electric AF-300 Mini Startup Manual page 53

Hide thumbs Also See for Fuji Electric AF-300 Mini:
Table of Contents

Advertisement

LED
Monitor
Display contents
Display
5_00
Accumulated running time
5_01
DC voltage at intermediate circuit
5_03
Max. temperature of heat sink
5_04
Max. effective current
5_05
Capacity of the intermediate dc
circuit capacitor
5_06
Accumulated running time of
electrolytic capacitor on the printed
circuit board/s
5_07
Accumulated run time of the cooling
fan
5_08
Number of startups
5_11
Number of RS485 errors
5_12
RS485 error contents
5_14
ROM version of drive
5_16
ROM version of keypad panel
Table 3.12 Maintenance Display Items
Description
Shows the accumulated power-on time of the drive.
Unit: thousands of hours. When the total ontime is less than 10,000 hours (display:
0.001 to 9.999), it is possible to check data in hourly units.
When the total time is 10,000 hours or more (display: 10.00 to 65.53), the display will
change to units of 10 hours. When the total time exceeds 65,535 hours, the display will
be reset to 0 and the count will start again.
Shows the dc voltage at main intermediate circuit of the drive.
Unit: V (volts)
Shows the maximum temperature of the heat sink for every hour.
Unit: ºC
Shows the maximum effective current for every hour.
Unit: A (amperes)
Shows the factory default for capacity of the intermediate dc circuit capacitor as 100%.
Refer to Chapter 7 "MAINTENANCE AND INSPECTION" for details.
Unit: %
Shows the total use time for the capacitor mounted on the printed circuit board/s.
The display method is the same as for "accumulated run time."
However, when the total time exceeds 65,535 hours, the count stops and the display
remains at 65.53.
Shows the accumulated operating time of the cooling fan.
The cooling fan ON/OFF control (function code H06) is effective, so the time when the
fan is stopped is not counted.
The display method is the same as for "accumulated run time."
However, when the total time exceeds 65,535 hours, the count stops and the display
remains at 65.53.
The motor run times (the number of times the drive running command is set to ON) are
calculated and displayed.
1.000 indicates 1,000 times. When any number ranging from 0.001 to 9.999 is
displayed, the display increases by 0.001 per startup, and when any number from 10.00
to 65.53 is displayed, the display increases by 0.01 every 10 startups.
Shows the total number of times and RS485 communications error has occurred after
the power is turned on.
Once the number of errors exceeds 9.999, the display (count) returns to 0.
Shows the latest error that has occurred with RS485 communications in hexadecimal
format.
Refer to the user's manual of RS485 communication.
Shows the ROM version of the drive as a 4-digit display.
Shows the ROM version of the keypad panel as a 4-digit display. (For remote keypad
only.)
3-17