Setting The Function Codes - "Data Setting - GE Fuji Electric AF-300 Mini Startup Manual

Hide thumbs Also See for Fuji Electric AF-300 Mini:
Table of Contents

Advertisement

(4) Jog (Inch) the Motor
In Run mode, pressing the
The JoG appears on the LED monitor.
To return the drive from the ready-to-jog state to the usual running state, press the
Using the external input signal command (JOG) also allows the transition between the ready-to-jog state and usual
running state.
REFERENCE: Refer to function codes E01 to E03 in Chapter 5 for details.
During jogging, the jogging frequency (C20) and acceleration/deceleration time for jogging (H54) will apply. They are
exclusively prepared for jogging and required to be set up individually.
When jogging the motor from the keypad, the drive will only run while the
moment the
key is released, the drive will decelerate and stop the motor.
NOTE: The transition ( +
drive is at a halt.
3.4 Setting the Function Codes – "Data setting"
Menu #1 "Data setting" in Program mode allows you to set function codes for making the drive functions match
your needs.
The table below lists the function codes available in the AF-300 Mini. The function codes are displayed on the LED
monitor on the keypad as shown below.
Function code group
F codes
(Fundamental functions)
E codes
(Extension terminal functions)
C codes
(Control functions of frequency)
P codes
(Motor parameters)
H codes
(High performance functions)
J codes
(Application functions)
y codes
(Link functions)
REFERENCE: Refer to Chapter 5 "FUNCTION CODES" for details on the function codes.
Function codes that require simultaneous keying
To change data for function codes F00 (Protect data) and H03 (Initialize data), simultaneous keying operation is
necessary-- +
keys or
+ keys at the same time (simultaneous keying) can make the drive ready for jogging.
keys) between the ready-to-jog state and usual running state is enabled only when the
Function Code Group
ID number in each function code group
Table 3.5 List of AF-300 Mini Function Codes
Function
Function
code
F00 to F51
Basic functions To be used for basic motor running.
E01 to E99
Terminal
functions
C01 to C52
Frequency
control
functions
P02 to P99
Motor
parameters
H03 to H98
High level
functions
J01 to J06
Application
functions
y01 to y99
Link functions
+
keys. This prevents data from being lost by mistake.
+
key is held down, and contrarily the
Description
To be used to select the functions of the control circuit terminals.
To be used to set functions related to the LED monitor display.
To be used to set application functions related to frequency
commands.
To be used to set special parameters for the motor capacity, etc.
To be used for high added value functions and complicated
control, etc.
To be used for PID control.
To be used for communications
3-9
keys simultaneously.

Advertisement

Table of Contents
loading

Table of Contents