Troubleshooting - FSP Technology iFP Series Manual Manual

Line-interactive ups
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
EN
Safety caution
This UPS utilizes voltage that may be hazardous. Do not attempt
to disassemble the unit. The unit contains no user replaceable
parts. Only factory service personnel may perform repairs.
This pluggable type A equipment with battery already installed by
the supplier is operator installable and may be operated by
laymen.
The mains socket outlet that supplies the UPS shall be installed
near the UPS and shall be easily accessible.
During the installation of this equipment it should be assured that
the sum of the leakage currents of the UPS and the connected
loads does not exceed 3.5mA.
Connection to any other type of receptacle other than a two-pole,
three-wire grounded receptacle may result in shock hazard as
well as violate local electrical codes.
In the event of an emergency, press the "OFF" button and
disconnect the power cord from the AC power supply to properly
disable the UPS.
Do not allow any liquids or any foreign object to enter the UPS.
Do not place beverages or any other liquid-containing vessels on
or near the unit.
This unit intended for installation in a controlled environment
(temperature controlled, indoor area free of conductive
contaminants). Avoid installing the UPS in locations where there
is standing or running water, or excessive humidity.
Do not plug the UPS input into its own output.
Do not attach a power strip or surge suppressor to the UPS.
Do not attach non-computer-related items, such as medical
equipment, life-support equipment, microwave ovens, or vacuum
cleaners to UPS.
Do not dispose of batteries in a fire as they may explode.
Internal battery voltage is 12VDC.Sealed, lead -acid, 6-cell battery.
A battery can present a risk of electrical shock and high short
circuit current. The following precautions should be observed
when working on batteries:
1) Remove watches, rings, or other metal objects from the hands.
2) Use tools with insulated handles.
3) Wear rubber gloves and boots.
4) Do not lay tools or metal parts on top of batteries.
5) Disconnect charging source prior to connecting or
disconnecting batteries terminal.
Servicing of batteries should be performed or supervised by
personnel knowledgeable of batteries and the required
precautions. Keep unauthorized personnel away from batteries.
When replacing batteries, replace with the same number and type
of sealed lead-acid battery.
Do not open or mutilate the battery or batteries. Release
electrolyte is harmful to the skin and eyes. It may be toxic.
Attention, hazardous through electric shock. Also with dis -
connection of this unit from the mains, hazardous voltage still may
be accessible through supply from battery. The battery supply
should be therefore disconnected in the plus and minus pole at
the connectors of the battery when maintenance or service work
inside the UPS is necessary.
To reduce the risk of overheating the UPS, do not cover the UPS'
cooling vents and avoid exposing the unit to direct sunlight or
installing the unit near heat emitting appliances such as space
heater or furnaces.
Unplug the UPS prior to cleaning and do not use liquid or spray
detergent.
FSP Manual Guide
Nothing is
displayed on
LCD panel.
The UPS
always on
battery mode.
The UPS
continuously
beeps.
Backup time
too short.
400VA/600VA/800VA
Model
Capacity
Input voltage
Input Voltage
Range
Output Voltage
Regulation
Transfer Time
Waveform
Battery Type
Battery Number
Charging Time
Dimension(mm)
Net Weight (kgs)
Humidity
Noise Level
*Specifications are subject to change without notice.
1000VA/1500VA/2000VA
Model
Capacity
Input voltage
Input Voltage
Range
Output Voltage
Regulation
Transfer Time
Waveform
Battery Type
Battery Number
Charging Time
Dimension(mm)
Net Weight (kgs)
Humidity
Noise Level
*Specifications are subject to change without notice.

Troubleshooting

Problem
Possible Cause
The UPS is not
on.
Battery voltage
is too low.
Battery fault.
Power cord
loose.
Please check
the fault code
for the details.
Battery voltage
is too low.
Overload.
Battery defect.
Specification
iFP 400
400VA/
240W
12V/4.5Ah
1
4 hours recover to 90% capacity
3.55
0-90% RH @ 0-40°C non-condensing)
iFP 1000
1000VA/
600W
12V/7Ah
2
4-6 hours recover to 90% capacity
8.2
0-90% RH @ 0-40°C non-condensing)
Line-interactive UPS
iFP 400VA~2KVA
Solutions
Press the power switch again to
turn on the UPS.
Charge the battery at least 6
hours.
Replace the battery.
Re-plug the power cord.
Please check the fault code for
the details.
Charge the battery at least 6
hours.
Remove some unnecessary
loads. Before reconnecting
equipment, please verify that the
load matches the UPS capability
specified in the specs.
Replace the battery.
iFP 600
iFP 800
600VA/
800VA/
360W
480W
220/230/240 Vac
140-290 Vac
± 10%(bat mode)
Typical 2-6 ms
Simulated Sinewave
12V/7Ah
12V/9Ah
1
1
300 x 101 x 142
4.2
4.9
Less than 40dB
iFP 1500
iFP 2000
1500VA/
2000VA/
900W
1200W
220/230/240 Vac
140-290 Vac
± 10%(bat mode)
Typical 2-6 ms
Simulated Sinewave
12V/9Ah
12V/9Ah
2
2
320 x 130 x 182
10.4
11
Less than 40dB

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ifp 400Ifp 600Ifp 800Ifp 1000Ifp 1500Ifp 2000

Table of Contents