Zener 8000 Application Manual page 17

Pid irrigator control
Hide thumbs Also See for 8000:
Table of Contents

Advertisement

Application SW08024: PID Irrigator
Parameters programmed by the Application:
The following parameters are automatically programmed by the 'Application' when it is loaded. They are
listed below for reference purposes only.
Application Menu:
1.
"Rated motor amps"
B02= ?
2.
"Overload current"
D020= ?
3.
"Motor RPM"
B04= ?
4.
"Transducer units" = "psi"
H08= 1
5.
"Transducer scale" = 200psi
H09= 200.0
6.
"Pressure Ref 1" = 100psi
F100= 50.0
7.
"Pressure Ref 2" = 100psi
F100= 50.0
8.
"Pressure Ref 3" = 100psi
F100= 50.0
9.
"Pressure Ref 4" = 100psi
F100= 50.0
10. "Pressure Tol." = 25%
H131= 250
11. "Pressure Q time" = 30sec
H132= 30
12. "Low Bore Timeout" = 0sec
G070= 0
13. "No flow Q time" = 20sec
G252= 20
14. "Hi Pressure Lvl" = 180psi
H111=180.0
15. "Minimum Speed " = 0Hz
C01= 0
16. "Pipe Fill" = DISABLED
H120= 0
17. "Fill Speed(Hz)" = 40Hz
H123=40
18. "Fill to Level" = 80psi
H122=80.0
19. "Fill Time(s)" = 40sec
H121=40
Other Preset Parameters
C030= 3.0 //1 sec Accel
C031= 3.0 //1 sec Decel
C032= 1 //1sec Accel & Decel to Min Hz
C033= 1 // Dual ramp
F010= 2 //Remote ref: PID-A Opt
F061= 7 //USER REF1: PRESET1
F062= 8 //USER REF2: PRESET2
F0631=22 //Selector 1: D2(33)
F0630=26 //Selector 2: D1(31)
F1001=1 //PRESET1..4 units: PID-A
F1011=1
F1021=1
F1031=1
G108= 2 //AI(32,34) config: 4 to 20mA
Page 16 Document: IM00160A
15/07/19
// Pressure Error Trip config
G230= 2 //UA1 active in PID closed loop
G231= 101 //UA1 signal: "PV-A OutOfReg"
G232= 0 //no delay
G233= "UA1:PRESSURE ERR"
// Siganl lost Trip
G106= 2.0 //AI(32,34) cmp lo thresh = 2.0mA
G240= 1 //UA2 trip active with RUN cmd
G241= 64 //UA2 signal: Lo AI(32,34)
G243= "UA2: SIGNAL LOST"
// No Flow Trip config
G250= 1 //Run command
G251= 31 //UA3 signal: ~D3(35)
G253= "UA3: NO FLOW "
// High Pressure Trip config
G260= 0 //UA1 trip always active
G261= 72 //UA1 signal: PV-A OVER
G262= 0 // No time delay on this trip
G263= "UA4: HI PRESSURE"
// Low Bore config
G271=55 //~TMR1
G272=" -DRY- "
G01=7 //Custom
I02=95 //Logic Block 1
I201=10 //D2(3)
I202=54 //TMR1
I203=17 // LB1 logic
G071=2 //TMR1 mode: Delay ON Init
G0720=0 //TMR1 IN2=ON
G0721=34 //TMR1 IN1=D4(37)
// PID config
H01= 200.0,"Prop. band value"
H02= 2.00,"Integrator time"
H06= 15 //PID-A SV: REF SEL
H07= 1 //PID-A PV: AI(32,34)
H102= 1 //Resume: by PV threshold
J02 = 2 //display: PID disp