FIRE DOOR CONTROL SOLUTIONS
TECHNICAL MANUAL
CENTRAL UNIT RZ-24-05
You can find the current version of our manual on our website under «Downloads»:
https://en.dictator.de/products/hold-open-systems-fire-protection-doors/central-units/central-unit-rz-24-05/

Advertisement

Table of Contents
loading

Summary of Contents for Dictator RZ-24-05

  • Page 1 FIRE DOOR CONTROL SOLUTIONS TECHNICAL MANUAL CENTRAL UNIT RZ-24-05 You can find the current version of our manual on our website under «Downloads»: https://en.dictator.de/products/hold-open-systems-fire-protection-doors/central-units/central-unit-rz-24-05/...
  • Page 2: Table Of Contents

    5.3 Configuration of the DIP switches 5.4 Assembly of the RZ-24-05 6. Placing the hold-open system into operation 7. Functioning / Adjustment instructions for RZ-24-05 7.1 Functions of the RZ-24-05 7.2 Troubleshooting DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
  • Page 3: General Safety Instructions

    1. General safety instructions 1.1 GENERAL SAFETY INSTRUCTIONS The RZ-24-05 central is a power supply with integrated tripping device for hold-open systems on fire and smoke protection doors. Only trained professionals may effect the installation; e.g. only a qualified electrical technician may connect the power supply to the mains.
  • Page 4: General Regulations For Hold-Open System

    If not, an additional detector is required. 2.2 OPERATIONAL LIFE To ensure the correct functioning of the hold-open system, the DICTATOR smoke and heat detec- tors have to be replaced after a maximum of 8 years of operational life. In Germany the DIN 14677 regulates the replacement obligation of fire detectors in hold-open systems.
  • Page 5: Components Of Hold-Open System With

    Magnet (DICTATOR electromagnets EM GD 50 to EM GD 70 - see separate catalogue pages) Push button of the RZ-24-05 central, further push button switches can be connected in the detector loop, e.g. part no. 040005 DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
  • Page 6: Information About The Rz-24-05 Central Unit

    Some parts inside the casing are energized with hazardous voltage during operation! May be opened only by professionals when being de-energized (the power supply of the RZ-24-05 is cut!!) DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
  • Page 7: Technical Data Of The

    IP rating IP 30 IMPORTANT In total the RZ-24-05 central provides 0.5 A for the supply of the con- nected fire detectors, magnets etc. In case the maximum power consumption is exceeded, the RZ-24-05 will automatically switch off. This also happens when it is overheated!
  • Page 8: Electrical Connection & Configuration Of Hold-Open System With

    Flash buzzer (24 VDC, max. 300 mA) (optional) Power pack optional Ill. 2 Push button Electromagnets (24 VDC, in total max. RM/WM 4000 240 mA) RM/WM 4000 RM/WM 4000 DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
  • Page 9: Terminal Assignment

    Technical manual: Central unit RZ-24-05 5.2 TERMINAL ASSIGNMENT The RZ-24-05 has 14 terminals. The maximum permissible wire thickness is 0.75 mm². The terminals may only be loosened with a special tool, part no. 040565, which is available sep- arately. A normal screwdriver will damage the terminals!
  • Page 10: Configuration Of The Dip Switches

    For this purpose, 24 V are briefly applied to the input. Central closing can be used to close doors (only with electromagnets) without triggering the detection loop of the RZ-24-05. This function is not a closing in case of fire, but only realizes the closing of the fire and smoke protection closures, e.g.
  • Page 11: Placing The Hold-Open System Into Operation

    With correct connection => the red LED (3) on the housing lights. Reset the central unit with the RESET button (2) on the housing cover. Now the system is ready for operation. Ill. 5 DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
  • Page 12: Assembly Of The

    "warning light" output is switched on. LED indicator "Ready" The "ready" LED indicator lights up green when the RZ-24-05 detector loop is ready (not trig- gered). The "electromagnet" output is switched on, the "warning light" output is switched off.
  • Page 13: Troubleshooting

    Error Measure Detection loop cannot Check whether the RZ-24-05 can be reset with a 3.9 kΩ resistor be reset on terminals and 2. If not, check whether the control module is correctly inserted in the terminal board. If the problem persists, replace the control module.