Page 1
FIRE DOOR CONTROL SOLUTIONS TECHNICAL MANUAL CENTRAL UNIT RZ-24-05 You can find the current version of our manual on our website under «Downloads»: https://en.dictator.de/products/hold-open-systems-fire-protection-doors/central-units/central-unit-rz-24-05/...
5.3 Configuration of the DIP switches 5.4 Assembly of the RZ-24-05 6. Placing the hold-open system into operation 7. Functioning / Adjustment instructions for RZ-24-05 7.1 Functions of the RZ-24-05 7.2 Troubleshooting DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
1. General safety instructions 1.1 GENERAL SAFETY INSTRUCTIONS The RZ-24-05 central is a power supply with integrated tripping device for hold-open systems on fire and smoke protection doors. Only trained professionals may effect the installation; e.g. only a qualified electrical technician may connect the power supply to the mains.
If not, an additional detector is required. 2.2 OPERATIONAL LIFE To ensure the correct functioning of the hold-open system, the DICTATOR smoke and heat detec- tors have to be replaced after a maximum of 8 years of operational life. In Germany the DIN 14677 regulates the replacement obligation of fire detectors in hold-open systems.
Magnet (DICTATOR electromagnets EM GD 50 to EM GD 70 - see separate catalogue pages) Push button of the RZ-24-05 central, further push button switches can be connected in the detector loop, e.g. part no. 040005 DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
Some parts inside the casing are energized with hazardous voltage during operation! May be opened only by professionals when being de-energized (the power supply of the RZ-24-05 is cut!!) DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
IP rating IP 30 IMPORTANT In total the RZ-24-05 central provides 0.5 A for the supply of the con- nected fire detectors, magnets etc. In case the maximum power consumption is exceeded, the RZ-24-05 will automatically switch off. This also happens when it is overheated!
Technical manual: Central unit RZ-24-05 5.2 TERMINAL ASSIGNMENT The RZ-24-05 has 14 terminals. The maximum permissible wire thickness is 0.75 mm². The terminals may only be loosened with a special tool, part no. 040565, which is available sep- arately. A normal screwdriver will damage the terminals!
For this purpose, 24 V are briefly applied to the input. Central closing can be used to close doors (only with electromagnets) without triggering the detection loop of the RZ-24-05. This function is not a closing in case of fire, but only realizes the closing of the fire and smoke protection closures, e.g.
With correct connection => the red LED (3) on the housing lights. Reset the central unit with the RESET button (2) on the housing cover. Now the system is ready for operation. Ill. 5 DICTATOR Technik GmbH · +49 (0)821 246730 · info@dictator.de · en.dictator.de · 20.05.13...
"warning light" output is switched on. LED indicator "Ready" The "ready" LED indicator lights up green when the RZ-24-05 detector loop is ready (not trig- gered). The "electromagnet" output is switched on, the "warning light" output is switched off.
Error Measure Detection loop cannot Check whether the RZ-24-05 can be reset with a 3.9 kΩ resistor be reset on terminals and 2. If not, check whether the control module is correctly inserted in the terminal board. If the problem persists, replace the control module.
Need help?
Do you have a question about the RZ-24-05 and is the answer not in the manual?
Questions and answers