Disposal
Technical data
Functional data
general
Switching function
Degree of protection
Environmental conditions
Standards and Directives
Environmental
compatibility
Dimensions / Weight
Material
Housing color
Siemens
Hindustan Hydraulics & Pneumatics, Chennai - 01.
Building Technologies
Contact person : V. Anandha krishnan - 98409 21885
The device is considered an electronics device for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
Dispose of the device through channels provided for this purpose.
Comply with all local and currently applicable laws and regulations.
Field of use
Permissible media
Medium temperature
Piping diameter
Nominal pressure
Contact
Type of switch
Max. contact rating
Max. switching capacity
Length of connecting cable/cross section
External supply line protection (EU)
Switching point adjustment
Setting range
Protection class
Housing
Storage, transportation, operation
Temperature
Humidity
Product standard
EU Conformity (CE)
The product environmental declaration CE1E1596
environmentally compatible product design and assessments (RoHS compliance,
materials composition, packaging, environmental benefit, disposal).
Excl. packaging
Switching unit/connecting cable
Housing and paddle system/piping
*) Applies to delivery state (switching function can be inverted as needed).
**) The documents can be downloaded from http://siemens.com/bt/download.
Flow switch QVE1902.0..
All liquids
(not suitable for ammonia)
-20...100 °C (Medium may not freeze)
DN 10...25
PN 10
(piping approved for PN 25)
Closes as flow increases
Opens as flow decreases
Reed contact
AC 230 V, 1 A / DC 48 V, 1 A
26 VA or 20 W
2
1.5 m / 0.5 mm
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to
or
Power source with current limitation of
max. 10 A
Manual, set at the factory to the middle of
the setting range
See Sizing on page 2
II according to EN 60730-1
IP65 according to EN 60529
0...70 °C
<95 % r.h.
EN 60204-1
Safety of machinery - Electrical
equipment of machines
**)
CM1T1596xx
**)
contains data on
See under "Dimensions and weight"
Polyamide / PVC
PPE+PS Noryl FE1630PW / brass
Black
Phone : 2534 3066, 2534 5625, 2534 5587
E-Mail : hhp@hindustanhydraulic.in
*)
*)
5 / 6
CM1N1596en
2017-02-16