Parameters Programming; Anomaly Warning - omi EL 36 Instruction And Maintenance Manual

Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 5
3.1.2 CONDENSATE DISCHARGE PARAMETERS PROGRAMMING
Push the SET key for 10 seconds to enter the parameters configuration menu: the display will show in
sequence the set point value, the code of the first modifiable parameter (C8) and its value).
Only if strictly necessary, use the UP and/or DOWN keys to change the displayed parameter value.
Press the SET key to store the previously changed parameter value or to browse the parameters
without changing them.
15 seconds after the last performed operation, the controller will return automatically to the normal
operation mode.
PARAMETER
C8
C9
NOTE: Changes entered for timing values will be effective only after exiting the programming, while changes to
other variables will be immediately effective.
Please remember that eventual changes to the configuration parameters of the machine could negatively affect
its efficiency. Thus, changes have to be arranged in collaboration with the manufacturer.
IT'S FORBIDDEN TO MODIFY THE OTHER CONFIGURATION PARAMETERS OF THE ELECTRONIC
CONTROLLER WITHOUT THE SERVICE CENTER'S AUTHORIZATION AND COLLABORATION.

3.1.3 ANOMALY WARNING

The controller is capable to recognize certain types of anomalies to the drying circuit. In such cases, an alarm message
will blink on the display, alternated to the current dew – point value.
MESSAGE
(BLINKING)
High Dew – point value
HtA
Very high Dew – point value
Ht2
LtA
Low Dew – point value
Interruption or short circuit on
PF1
the PTC probe input line
ESA
Energy saving mode activated
ES2
Series of alarms very close to
ASt
Note: PF1 has priority on all other alarm messages.
Cod. 710.0151.01.00 Rev0B – 08.2012
DESCRIPTION
Delay between condensate
discharges
Time required for condensate
discharge
WARNING FOR USER:
CAUSE
(delayed alarm)
(immediate alarm)
each other
RANGE
1 ÷ 999 (min)
1 ÷ 999 (sec)
OUTPUTS
Alarm output ON
Refrig. Compressor output OFF
Fan output ON
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output OFF
Refrig. Compressor output OFF
Fan output OFF
Discharge cycle standard
Alarm output ON
Refrig. Compressor output OFF
Fan output ON
Discharge cycle standard
ENGLISH
SET VALUE
1
1 ÷ 3
ACTIONS
Resettable by switching off the
control board when dew-point
returns to preset range.
If it persists call our Service
Centre.
Automatic reset when dew-
point returns to preset range.
If it persists call our Service
Centre.
Resettable by switching off the
control board and replacing the
faulty probe.
Call our Service Centre.
No action necessary.
Automatic Reset
Call our Service Centre.