After selecting all four zones or pressing the FUNCTION button, the following will appear in the display window:
O U T P
U T
E N A B L E D

Output Enable/Disable

This display allows the user to ENABLE or DISABLE any of the output circuits. NFPA 72 prohibits the use of a software
disconnect for RELEASE CIRCUITS. A physical means of disconnecting a RELEASE CIRCUIT shall be used, such as the Potter
RCDS-1.
SET
After selecting ENABLED or DISABLED, press the SET button to set and move to the
next output.
SELECT
Press the SELECT button to toggle between ENABLED or DISABLED.
FUNCTION
To skip to the next function, press the FUNCTION button.
After selecting all four outputs or pressing the FUNCTION button, the following will appear in the display
S
Y S
T
E M
N O R M A L

One Man Walktest

This display allows the user to select system mode NORMAL or ONE MAN WALKTEST by pressing the SELECT button to
toggle back and forth from NORMAL to ONE MAN WALKTEST. When the desired mode is displayed, press the SET button.
If ONE MAN WALKTEST is selected for test purposes, the display must be restored to the NORMAL setting after the test is
completed by toggling to it using the SELECT button.
WARNING
After 30 minutes of no activity the panel
automatically reverts to normal.
SET
After selecting NORMAL or ONE MAN WALKTEST, press the SET button to set that mode.
SELECT
Press the SELECT button to toggle between NORMAL and CROSS ZONED.
FUNCTION
Press the FUNCTION button to skip to the next function.
After selecting the operating mode or pressing the FUNCTION button a display similar to the following will appear in the display
window:
P
R O G R
A M
VFR-400 • 5403548 • REV W • 8/17
# 1
Disabling any input or outputs will create a trouble condition on the panel.
Disabling a releasing circuit will create a supervisory condition.