Applicable Controls - Toshiba RAV-HM401CTP-E Installation Manual

Hide thumbs Also See for RAV-HM401CTP-E:
Table of Contents

Advertisement

<Multi-indoor-unit connection>
Power supply wiring for multiple indoor units
1
2
3
10 mm
10 mm
50 mm
30 mm
Earth wire
Connecting wire
Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Terminal block for
remote controller
Terminal block
wiring of indoor unit
Remote
A
A
controller
B
B
unit
Remote controller wire (Locally procured)
Run the remote controller wire
Remote controller wire
through the cord clamp.
Power supply wiring for
multiple indoor units
Indoor/Outdoor
connecting wires
See the figure on the left for
connecting wires to the
terminal block.
Indoor/Outdoor connecting wires
Remote controller
wire
– 17 –
8

Applicable controls

• For using the wired remote controller RBC-AMS55E*,
refer to the Owner's Manual attached to the wired
remote controller.
REQUIREMENT
• When you use this air conditioner for the first time,
it takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes approx. 5 minutes until the remote controller
becomes available.
Approx. 5 minutes
"SETTING"
"SETTING"
Power on
flashes
goes out
<When power is turned on for the second
(or later) time>
It takes approx. 1 minute until the remote controller
becomes available.
Approx. 1 minute
"SETTING"
"SETTING"
Power on
flashes
goes out
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
* The settings cannot be changed using the wireless
remote controller, sub remote controller,
or remote-controller-less system (for central remote
controller only). Therefore, install the wired remote
controller to change the settings.
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU1
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
Remote
controller is
Set only the Code No. shown in the following table:
available
Do NOT set any other Code No.
If a Code No. not listed is set, it may not be possible
to operate the air conditioner or other trouble with the
product may result.
Remote
controller is
available
1
Push and hold menu button and [ ] setting
button simultaneously for 10 seconds or more.
• After a while, the display flashes as shown in the
figure. "ALL" is displayed as indoor unit numbers
during initial communication immediately after
the power has been turned on.
Indoor unit No.