2
Each time [ ] [ ] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs. The
indoor unit can be confirmed for which to change
settings.
3
Push OFF timer button to confirm the selected
indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
] with
[ ] [ ] setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
] with
[ ] [ ] setting button.
6
Push OFF timer button.
By doing so, the setup is completed.
• To change other settings of the selected indoor
4
unit, repeat from Procedure
.
7
When all the settings have been completed,
push ON/OFF button to determine the settings.
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit, repeat
1
from Procedure
.
Installing indoor unit on high
ceiling
When the height of the ceiling to be installed exceeds
3.5 m, adjustment of air volume is necessary.
Set up the high ceiling.
• Set according to the basic operation procedure
1
2
3
4
5
6
(
).
• CODE No. in Procedure specifies [5d].
• Select [SET DATA] in Procedure from "List of
installable ceiling height" in this Manual.
4
• For the CODE No. in Procedure
, specify [5d].
5
• For the SET DATA in Procedure
, select the
SET DATA of ceiling height to be set up from the
table on the below.
Model
HM
SET DATA
✱✱✱
Standard
Up to 3.5 m
0000
(Factory default)
High ceiling (1)
Up to 4.3 m
0003
◆ Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the indoor unit P.C. board.
* Once the setting is changed, setting to 0001 is
possible, however setting to 0000 requires a
setting data change to 0000 using the wired remote
controller (separately sold) with the normal switch
setting (factory default).
SW501-2
SW501-1
MCU(IC501)
SET DATA
SW501-1
SW501-2
0000
OFF
OFF
(Factory default)
0003
OFF
ON
To restore the factory defaults
To return the DIP switch settings to the factory
defaults, set SW501-1 and SW501-2 to OFF, connect
a separately sold wired remote controller, and then set
the data of CODE No. [5d] to "0000".
Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
4
• For the CODE No. in Procedure
, specify [01].
5
• For the [SET DATA] in Procedure
DATA of filter sign term from the following table.
SET DATA
Filter sign term
0000
None
0001
150H
2500H
0002
(Factory default)
0003
5000H
0004
10000H
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other device to circulate
heat air near the ceiling.
Follow to the basic operation procedure
1
2
3
4
5
6
(
).
4
• For the CODE No. in Procedure
, specify [06].
5
• For the set data in Procedure
, select the SET
DATA of shift value of detection temperature to be set
up from the following table.
SET DATA
Detection temperature shift value
0000
No shift
0001
+1 °C
+2 °C
0002
(Factory default)
0003
+3 °C
0004
+4 °C
0005
+5 °C
0006
+6 °C
– 18 –
Remote controller sensor
The temperature sensor of the indoor unit senses room
temperature usually. Set the remote controller sensor
to sense the temperature around the remote controller.
Select items following the basic operation procedure
1
2
3
4
5
(
[32]
, select the SET
• Specify
for the Code No. in Procedure
• Select the following data for the set data in
5
Procedure
.
SET DATA
Remote controller sensor
0000
Not in use (Factory default)
0001
When
flashes, the remote controller sensor is defective.
Select the set data [0000] (not in use) or replace the remote
controller.
Communication type
When connecting to the central control device
dedicated to TCC-Link, it is necessary to change to
TCC-Link.
Follow to the basic opreration procedure
1
2
3
4
5
(
[FC]
• Specify
for the Code No. in Procedure
• Select the set data [0000] (TCC-Link) in
5
Procedure
.
SET DATA
Communication type
0000
0004
TU2C-Link (Factory default)
Fan speed setting when
thermostat-OFF in cooling
mode
Set the fan speed when the room temperature reaches
the set temperature in the cooling mode.
Follow to the basic opreration procedure
1
2
3
4
5
(
[9A]
• Specify
for the Code No. in Procedure
• Select the following data for the set data in
5
Procedure
.
Fan speed when thermostat-OFF
SET DATA
0000
Remote controller setting
Extremely low speed (UL)
0001
6
7
).
4
.
In use
6
7
).
4
.
TCC-Link
6
7
).
4
.
in cooling mode
(Factory default)