Before installation
1
Removal of air intake grille
1) Remove the screws of air intake grille fixing
knob on a side of each filter.
2) Slide the air intake grille fixing knobs (two
positions) toward the arrow direction (OPEN),
and then open the air intake grille.
3) With the air intake grille open, hold the hinge
from above and below with one hand and take
out the air intake grille with the other hand
while gently pushing it. (There are two air
intake grilles.)
Hinge
Air intake grille
Air intake grille
fixing knob
2
Removal of side panel
After removing the side panel fixing screws
(1 each at right and left), slide the side panel
forward and then remove it.
Side panel
Side panel fixing screw
Louver
Slide forward.
CAUTION
Cushion
Cushions are inserted between the side panel and
hanging hook for transportation.
(In the two places shown above)
Remove them before installation.
Draw-out direction of pipe /
wire
Decide installation place of the unit and draw-out
direction of pipe and wire.
Pipe knockout hole
In case of taking pipe from the rear side
* Cut off the groove section with a plastic cutter.
Rear cover
>PP< FRO
Opened when refrigerant pipe is
Ø100
taken out from the rear side
Opened when only drain pipe is
taken out from the rear side
Grooves
<In case of taking pipe from right side>
* Cut off the groove section with a metal saw or plastic
cutter.
Side panel (Right)
<In case of taking pipe from left side>
Taking pipe from left side is applied only to the
drain pipe.
The refrigerant pipe cannot be taken out from the
left side.
* Cut off the groove section with a metal saw or plastic
cutter.
Groove
Side panel (Left side)
– 10 –
<In case of taking pipe from upper side>
Taking pipe from upper side is applied only to the
refrigerant pipe.
When taking out the drain pipe from the upper side,
use a drain up kit sold separately.
Open the upper pipe draw-out port (Knockout hole)
shown in the external dimensions.
Make the diagonally shaded hole when
you do not use the Elbow Piping Kit.
Make only this knockout hole when
you use the separately sold Elbow
Piping Kit.
After piping, cut off the attached heat insulator of the
top plate to pipe shape, and then seal the knockout
hole.
Knockout hole of power wire
take-in port
Open the power wire take-in port (Knockout hole)
shown in the "External dimensions" and then mount the
Groove
attached bushing.