Siemens XTRI-S Installation Instructions Manual page 2

Addressable switch interface modules with dual isolators

Advertisement

To connect the XTRI to the DPU Programmer/Tester, insert the plug from the DPU cable provided with
the Programmer/Tester into the opening on the front of the XTRI shown in Figure 2. The plug has no
polarity and can be inserted into the holes at either direction.
CAUTION: To prevent potential damage to the DPU, DO NOT connect an XTRI to the DPU until all
connectors of the same polarity are removed from the device line of the XTRI.
Follow the instructions in the DPU Manual (P/N 315-033260) to program the XTRI to the desired
address. Record the device address on the address label, which comes with the product, and place it
on the module or on the XTRI front panel. The XTRI can now be installed and wired to the system.
Figure 2
Connecting the DPU Plug
WIRING SWITCHES AND EOL
CAUTION: Deactivate P2 circuit by either or both of the following: Using the PMI, bypass the circuit
being modified, and/or physically disconnect the circuit from the P2 source.
NORMALLY CLOSED PROGRAMMABLE SWITCHES
(SEE NOTES 1, 3, AND 4)
END OF LINE
RESISTOR
470 OHMS,
1% 1/2W
NOTES:
1.
There can be any number of normally closed or normally open switches.
2.
The end of line resistor must be located at the last switch.
3.
Do not wire a normally closed switch across the end of line resistor.
4.
Only for use with status applications.
Figure 3
Wiring Switches
A6V101055479_en--_a
PROGRAMMING HOLES
SLOT FOR
LOCATING
TAB
THERE IS NO
DIRECTIVITY
DESIGN FOR DPU
CONNECTION. IT
IS ALLOWED TO
INSERT THE PLUG
AT EITHER DIRECTION
2
firealarmresources.com
PLUG FROM
THE DPU
PROGRAMMER/
TESTER
NORMALLY OPEN PROGRAMMABLE SWITCHES
(SEE NOTES 1 AND 2)
END OF LINE
RESISTOR
470 OHMS,