9.2 Preparing and Installing the Reinforced Stool

Step No.
1
WARNING: Prior to installation of the Reinforced Stool, instruct the Civils
Contractor as to the correct orientation of all cabinet stools, ensuring all
cabinets on site will face the right way.
The reinforced stool is based on a normal controller cabinet stool and the installation
process is much the same.
WARNING: Although similar, the normal ST800, ST900 or ST950 cabinet stool
must not be used when installing the UPS Solution as it is not capable of
supporting the total weight of all cabinet elements.
1. Prepare the Reinforced stool by fitting the CET plate to the upward fold in the top
of the stool using the two bolts and fixings provided.
2. Have the stool concreted into place in site in accordance with 667/HE/45950/000.
See Figure 9-2.