Fitting And Connecting The Battery Housing Module - Siemens 667/HB/47750/000 General Handbook

Ups solution
Table of Contents

Advertisement

9.5 Fitting and Connecting the Battery Housing Module

Step No.
4
The Battery Housing Module design allows them to be stacked unto each other. A
varying number of battery housing modules can be fitted depending on specific site
requirements.
WARNING: Batteries MUST NOT be fitted within the Battery Housing module
during installation.
Figure 9-4: Battery Housing Modules stacked on the Reinforced Stool (Cabinet
Fitting the first Battery Housing Module:
1. Pass the first battery housing through the front door aperture of the cabinet outer
case and place unto the raised box section 'top hats' of the reinforced stool.
2. Align the countersunk holes in the bottom of the battery housing with the
threaded holes in the 'top hats', then secure into place using the Alan key and
fixings provided.
3. Pass the loose earth wire from the right side of the battery housing through the
opening in the housing bottom and secure to the marked earth stud on the box
section 'top hat' below.
Version
7
Last Editor
Ore Oluwatudimu
Document
UPS Solution General Handbook
Name
Copyright ã Siemens plc 2017 All Rights Reserved
UPS Cabinet
Fit and connect the Battery Housing module(s)
NOTE: Secure external cables from the CET plate to the cable
management holes in the left hand side of the Battery Housing modules as
each module is installed
Page 32 of 76
TS008468
Infrastructure and Mobility, Traffic Solutions
Battery Expansion Cabinet
removed)
Status
Date
Doc. No.
Sopers Lane, Poole, Dorset
BH17 7ER
Refer to
Section 9.5
ISSUED
31/01/2017
667/HB/47750/000

Advertisement

Table of Contents
loading