Example of ReportDataCmd
FPort:0x06
Bytes
Version
Version– 1 bytes –0x01——the Version of NetvoxLoRaWAN Application Command Version
DeviceType– 1 byte – Device Type of Device
The devicetype is listed in Netvox LoRaWAN Application Devicetype doc
ReportType – 1 byte –the presentation of the NetvoxPayLoadData,according the devicetype
NetvoxPayLoadData– Fixed bytes (Fixed =8bytes)
R718N3
0x4A
Ex1
Uplink data#1: 014A0124006400C81B5801
Uplink data#2: 014A0224010A0000000000
Current = Current * Multiplier
Current 1 = Current1 * Multiplier 1, 100*1=100 mA
Current 2 = Current2 * Multiplier 2, 200*1=200 mA
Current 3 = Current3 * Multiplier 3, 7000*10=70000 mA=70A
Example for MinTime/MaxTime logic:
Example#1 based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
Sleeping(MinTime)
Wakes up and collects data
REPORTS 3.6V
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BatteryVoltageChange
value.
1
1
DeviceType
ReportType
Battery
0x01
(1Byte, unit:0.1V)
Battery
0x02
(1Byte, unit:0.1V)
Wakes up and collects data
REPORTS 3.6V
1
Current1
Current2
(2Bytes,Unit:1mA)
(2Bytes,Unit:1mA)
Mulitplier2
(1Byte),the real current2
should convert with
Current* Multiplier
MaxTime
Sleeping(MinTime)
7
Var(Fix=8 Bytes)
NetvoxPayLoadData
Current3
(2Bytes,Unit:1mA)
Mulitplier3
(1Byte),the real current3
should convert with
Current* Multiplier
Wake up and collects data
REPORTS 3.6V
Mulitplier1(1Byte),
the real current1
should convert with
Current* Multiplier
Reserved(5Bytes,fixed
0x00)