Flexible Vent System - ECR International Dunkirk DCBF-75 Manual

Condensing gas fired boiler
Table of Contents

Advertisement

5.14 (3" /80 mm Only) Flexible Vent System
Flexible Pipe Minimum & Maximum Vent Lengths
3" [80 mm]
Diameter Pipe
Exhaust
Natalini
Intake
Exhaust
DuraVent
®
Intake
Exhaust
Centrotherm
Intake
Exhaust
Z-Dens
Intake
Single Wall Elbows - Equivalent Length
Vent Dia.
45° bend
90° bend
Flexible vent systems shall only be run
vertical. Horizontal runs before adapting
Note
to flexible must be rigid pipe.
• Follow venting manufacturer's instructions on
assembly and clearances to maintain.
• Maximum vent lengths based on equivalent
straight runs only. Include rigid pipe and fittings
in overall equivalent length calculations.
• Flexible venting installations use single wall
polypropylene to pass flue gasses to base of
chimney, then flexible venting to get them to
termination at the top.
• Combustion air is not supplied through masonry
chimney. Combustion air must be from outside
using 3" [80 mm] single wall polypropylene.
• Position boiler to use minimum of rigid single wall
polypropylene venting to the chimney.
• Avoid sharp bends in flexible venting.
5 - COMBUSTION AIR AND VENT PIPING
75/100/115/125/150
Min
Max
6 ft
75 ft
[1.8 m]
[22.8 m]
[1.8 m]
6 ft
50 ft [15.2 m]
[1.8 m]
[1.8 m]
6 ft
82 ft [24.9 m]
[1.8 m]
[1.8 m]
6 ft
50 ft [15.2 m]
[1.8 m]
[1.8 m]
6 ft
52 ft [15.8 m]
[1.8 m]
[1.8 m]
6 ft
50 ft [15.2 m]
[1.8 m]
[1.8 m]
NA
[1.8 m]
3" [80 mm]
0.82 ft [0.25 m]
1.64 ft [0.50 m]
FIGURE 5-33 - (3" / 80 mm Only) Flexible Venting
System CAN BE USED ON ALL SIZES
165/205
Min
Max
6 ft
50 ft
[15.2 m]
6 ft
50 ft
[15.2 m]
6 ft
50 ft
[15.2 m]
6 ft
50 ft
[15.2 m]
6 ft
50 ft
[15.2 m]
6 ft
50 ft
[15.2 m]
6 ft
50 ft
[15.2 m]
Combustion
Air
29
Vent Terminal
Flexible Vent
Rigid Vent
240013509 REV A, [03/15/2022]
Use Venting
Manufacturer
supplied base
support, not a
Tee