Mission Inverter
When the AC run in mute mode, the compressor will run with low frequency.
When the current is more than setting value, the current protection function will be activated and the
compressor will stop.
10.4.3.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different.
T 4
A +
A
B
C
D
E
10.4.3.3 Indoor fan running rules
When the compressor is on, the indoor fan can be set to high/med/low/auto. And the anti-cold wind
function has the priority.
The indoor fan is controlled as below:
Setting fan
T1-Td ℃(°F)
speed
A
H
B
C
D
M
E
F
G
L
H
I
Auto fan action in heating mode:
T 1
a
b
c
d
e
10.4.3.4 Defrosting mode
AC will enter the defrosting mode according to the value of temp. of T3 and the value range of temp.
change of T3 and also the compressor running time.
During the defrosting mode, the compressor keep running, indoor and outdoor motor will stop, defrost
lamp of the indoor unit will be lighted "
If any one of the following items is satisfied, the defrosting will finish and the machine will turn to
42
Actual fan speed
H+(H+=H+G)
H(=H)
H-(H-=H-G)
M+(M+=M+Z)
M(M=M)
M-(M-=M-Z)
L+(L+=L+D)
L(L=L)
L-(L-=L-D)
." Will be displayed.
DM16-01.01.22en
Service manual