Toshiba RB-RWS20-E Installation Manual page 20

Lite-vision plus remote controller
Table of Contents

Advertisement

Lite-Vision plus Remote Controller
Field setting menu
1.Test mode
2.Register service info.
3.Alarm history
4.Monitor function
5.FC setting
Return
Test mode
Test mode start.
Return
Yes
(1)
Room A
Test
Cool
Mode
Fan Speed
(2)
Room A
Test
(3)
Test mode
Test mode stop.
Return
Yes
Set
No
12:00
12:00
No
1
Push the [
"1. Test mode" on the "Field setting menu
screen, then push the "
F2] button.
Pushing the "
sets the test mode and the screen returns to the
field setting menu screen.
Push [
appears.
2
Push the [
test mode. The screen (1) shown in the left
appears. (The screen (2) appears when the
operation is stopped.)
Perform the test mode in the "Cool" or "Heat"
mode.
Temperature setting cannot be adjusted during
the test mode.
Check codes are displayed as usual.
3
When the test mode is finished, push the
[
] / [
mode" on the "Field setting menu" screen,
then push the "
button.
The screen (3) appears.
Pushing the "
stops the test mode screen and continues the
normal operation.
NOTE
The test mode stops after 60 minutes and the screen
returns to the normal / detailed display.
– 19 –
Installation Manual
] / [
] button to select
Set
Yes" [
Yes
CANCEL] twice, the screen (2)
ON / OFF] button to start the
] button to select "1. Test
Set" [
Set
Yes" [
Yes
Set" [
F1] button
F2]
F1] button