Nominal Data; Technical Features; Mounting Data; Transport And Storage Conditions - ebm-papst R2D220-AA24-09 Operating Instructions Manual

Hide thumbs Also See for R2D220-AA24-09:
Table of Contents

Advertisement

R2D220-AA24-09

3.2 Nominal data

Motor
M2D068-BF
Phase
3~
Nominal voltage / VAC
230
Connection
Δ
Frequency / Hz
50
Type of data definition
fa
Valid for approval /
CE
standard
Speed / min
-1
2450
Power input / W
68
Current draw / A
0.26
Min. back pressure / Pa
0
Max. ambient
55
temperature / °C
ml = max. load · me = max. efficiency · fa = running at free air
cs = customer specs · cu = customer unit
Subject to alterations

3.3 Technical features

Mass
1.4 kg
Size
220 mm
Surface of rotor
Uncoated
Material of impeller
Plastic PA6, fibreglass-reinforced
Number of blades
11
Direction of rotation
Clockwise, seen on rotor
Type of protection
IP 44
Insulation class
"F"
Humidity class
F0
Mounting position
any
Condensate discharge
None
holes
Operation mode
S1
Motor bearing
Ball bearing
Touch current acc.
< 0.75 mA
IEC 60990 (measuring
network Fig. 4, TN
system)
Cable exit
Axial
Protection class
I (if protective earth is connected by
customer)
Product conforming
EN 60335-1, motor does not have
to standard
factory-installed overheating protection
For cyclic speed loads, note that the rotating parts of the device
are designed for maximum one million load cycles. If you have
specific questions, contact ebm-papst for support.

3.4 Mounting data

For depth of screw, see chapter 3.1 Product drawing
; Secure the mounting screws against accidentally coming loose (e.g.
by using self-locking screws).
Strength class for
8.8
mounting screws
You can obtain additional mounting data from the product drawing if
necessary.
Item no. 10624-5-9970 · Revision 68158 · Release 2009-09-14 · Page 5 / 9
ebm-papst Mulfingen GmbH & Co. KG · Bachmühle 2 · D-74673 Mulfingen · Phone +49 (0) 7938 81-0 · Fax +49 (0) 7938 81-110 · info1@de.ebmpapst.com · www.ebmpapst.com
Operating instructions
3~
3~
3~
230
400
400
Δ
Y
Y
60
50
60
fa
fa
fa
CE
CE
CE
2600
2450
2600
82
68
82
0.24
0.15
0.14
0
0
0
55
55
55

3.5 Transport and storage conditions

; Use the device in accordance with its protection type.
Max. permissible
+ 80 °C
ambient motor temp.
(transp./ storage)
Min. permissible
- 40 °C
ambient motor temp.
(transp./storage)