Common Vent Maximum Equivalent Vent Lengths
For the table below:
Header is the main vent pipe into which several vents connect
Vent Length is the distance from the end of the header to the
vent termination.
Maximum vent length starts at the end of the header system.
Use 10 ft (3 m) as equivalent vent length for 90° elbows.
For use with CU199i internal (indoor) tankless water heaters only.
Common Vent Maximum Equivalent Vent Length
Rinnai Common Vent System or Schedule 40 PVC/CPVC
Water Heater
Model
CU199i
(REU-N3237FFC-US)
32
Max System
# Water
Heaters
BTU/HR
2
398,000
3
597,000
4
796,000
5
995,000
6
1,194,000
7
1,393,000
8
1,592,000
3 in.
3 in.
Vent Diameter
Vent Diameter
65 ft
Rinnai Commercial Hybrid System Installation and Operation Manual
Header
Vent Length
HEADER DIAMETER
4 in.
4 in.
6 in.
Vent Diameter
150 ft
65 ft
150 ft
70 ft
6 in.
6 in.
Vent Diameter
150 ft