Honeywell FS19X Series Installation Manual And Operating Manual page 25

Fire and flame detector
Table of Contents

Advertisement

Drawings
(continued)
Wiring and Terminal Connections (continued)
Fire Alarm Control Panel
Alarm
Input
Fault
Input
24 VDC (+)
24 VDC (-)
Typical Relay Output Wiring for Monitoring Separate Alarm and Fault Contacts
Fire Alarm Control Panel
Alarm &
Fault Input
24 VDC (+)
24 VDC (-)
Typical Relay Output Wiring for Monitoring Alarm and Fault Contacts on a single two-wire input
NOTES:
1. Cable shield must be grounded to "Earth Ground" at the Control Panel end only. Coil and tape the
cable shield at the Detector end.
2. Alarm relay contacts shown with no power applied. Alarm relay is normally De-Energized during
normal operation and with no Alarm. This relay will Energize during Alarm conditions.
3. Fault relay contacts shown with no power applied. During normal operation and with no Fault, this
relay will De-Energize and the N.O. (normally open) contacts will close.
4. EOL (End-Of-Line) device shall be installed as required and supplied by the Fire Alarm Panel.
Honeywell
Installation Guide and Operating Manual // Model FS19X™ & FS20X™ Series
Note 1
Note 4
EOL
Note 1
Figure 4-7
EOL
Note 4
Note 1
Figure 4-8
J2
1
2
3
N.C.
4
Alarm
Relay
5
Contacts
N.O.
(Note 2)
6
.
N.O
Fault
7
Relay
8
Contacts
(Note 3)
9
(+)
(-)
10
FSX Detector
J2
1
2
3
4
Alarm
5
Relay
N.O.
6
Contacts
(Note 2)
7
Fault
Relay
N.O.
8
Contacts
(Note 3)
9
(+)
(-)
10
FSX Detector
23