Safety Classiication; General Mounting Instructions; Mounting Of The Sensors; Installation In Zone 2: Particular Conditions - schmersal PROTECT SRB 101EXi-1R Operating Instructions Manual

Safety-monitoring module
Table of Contents

Advertisement

Operating instructions
Safety-monitoring module
Utilisation category to IEC/EN 60947-5-1:
Dimensions H x W x D:
The data specified in this manual is applicable when the component is
operated with rated operating voltage U
EX-relevant Data
EC-prototype test certificate:
- Designation:
EC-prototype test certificate:
- Designation:
IECEx:
- Designation:
INMETRO:
- Designation:
Maximum safety voltage U
:
m
Inputs:
Temperature class:
Voltage U
:
o
Current I
:
o
Capacity P
:
o
Separation (intrinsically safe / other circuits):
Gas group
II C
External capacity
26
36
Co (nF)
external inductivity
4.0 2.0 1.0 0.5 38.0 5.0 2.0 1.0 0.5 0.2
Lo (mH)
Reference values for cable to EN 60079-14
(cable with 2 or 3 conductors):
C ≈ 200 nF/km, L ≈ 1 mH/km (C ≈ 200 pF/m, L ≈ 1 µH/m)
Reference values for cable with 3 to 6 conductors:
C ≈ 400 nF/km, L ≈ 2 mH/km (C ≈ 400 pF/m, L ≈ 2 µH/m)
2.5 Safety classification
Standards:
PL:
Control category:
DC:
CCF:
PFH value:
SIL:
Service life:
AC-15: 230 V / 3 A
DC-13: 24 V / 3 A
100 mm x 22,5 mm x 121 mm
± 0%
e
.
TÜV 08 ATEX 7522
L II (2) G [Ex ib Gb] IIC
L II (2) D [Ex ib Db] IIIC
(Circuit in Zone 1, 21 / 2, 22)
TÜV 08 ATEX 7557 X
L II 3 G Ex nA nC IIC T5 Gc
(SRB in Zone 2)
IECEx TUR 15.0xxxx
[Ex ib Gb] IIC
[Ex ib Db] IIIC
Ex nA nC IIC T5 Gc
DNV 14.0041
[Ex ib Gb] IIB
[Ex ib Gb] IIC
[Ex ib Db] IIIC
253 VAC
(caution: Um is not a rated voltage!)
S11-S12, S21-S22, X1-X3:
[Ex ib Gb] IIC bzw. [Ex ib Db] IIIC
57,0 mA
478,8 mW (linear characteristic)
safe separation
according to
IEC/EN 60079-11
(ABTN NBR IEC 60079-11),
Voltage peak value 375 V
II B
46
49 160 180 230 280 350 412
EN ISO 13849-1, IEC 61508
99% (high)
> 65 points
≤ 2.00 x 10
20 years
The PFH values of 2.00 x 10
load (current through enabling contacts) and number of switching cyc-
les (n
) mentioned in the table below. At 365 operating days per year
op/y
and a 24-hours operation, this results in the below-mentioned switching
cycle times (t
) for the relay contacts.
cycle
Diverging applications upon request.
Contact load
20 %
40 %
60 %
80 %
100 %
3. Mounting

3.1 General mounting instructions

Mounting: snaps onto standard DIN rails to EN 60715.
Snap the bottom of the enclosure slightly tilted forwards in the DIN rail
and push up until it latches in position.
T5
33,6 V

3.2 Mounting of the sensors

The installation of the intrinsically safe current circuits must be executed
in accordance with the applicable standards IEC/EN 60079-14 (ABTN
NBR IEC 60079-14.
According to IEC/EN 60079-11 (ABTN NBR IEC 60079-11),
the following must be observed for the installation: a distance
of ≥ 6 mm must be observed between the terminals of the
intrinsically safe current circuits and other intrinsically safe
current circuits. Between the terminals of the intrinsically
safe current circuits and other, non-intrinsically safe current
circuits, a distance of ≥ 50 mm must be observed.
The commissioning and installation are to be executed by
qualified professionals only.

3.3 Installation in Zone 2: particular conditions

The devices must be installed in control or junction boxes, which meet
the requirements to IEC/EN 60079-15 (ABTN NBR IEC 60079-15) and
have at least protection class IP54 (Fig. 1). To respect temperature
class T5, the device must have a free volume of at least 2,400 cm³.
Please make sure that you have read and understood these operating
instructions and that you know all applicable legislations regarding
occupational safety and accident prevention prior to installation and
putting the component into operation.
The intrinsically safe current circuits of the device (light blue terminals)
may be lead in explosion-endangered areas. In this case, it must be
especially observed that they are safely separated from all non-intrinsi-
up to e
cally safe current circuits.
up to 4
The connection and separation of the connections of
non-intrinsically safe current circuits is not authorised
-8
/h
in explosion-endangered atmospheres.
up to 3
Only use a damp cloth to clean the enclosure.
The lifetime of the safety-monitoring related to
the ignition protection class "nC" is at least 15 years.
Upon expiration of this time, the safety-monitoring modu-
le must be replaced either returned to the manufacturer
for check-up!
The temperature specifications (–25 °C ≤ Ta ≤ +60 °C) of
the safety-monitoring module are related to a volume of the
control cabinet of at least approx. 2,400 cm³ for each SRB.
The distance with regard to other safety-monitoring module
imperatively must be at least approx. 5 cm.
EN
PROTECT SRB 101EXi-1R
-8
/h apply to the combinations of contact
n
t
op/y
cycle
525,600
1.0 min
210,240
2.5 min
75,087
7.0 min
30,918
17.0 min
12,223
43.0 min
3

Advertisement

Table of Contents