Accessories; Accessories Supplied With This Unit; Overview Of The Indoor Unit; Main Components - Daikin EKHBRD016ABV1 Installation Manual

Indoor unit for air to water heat pump system
Hide thumbs Also See for EKHBRD016ABV1:
Table of Contents

Advertisement

A
CCESSORIES

Accessories supplied with this unit

(See figure 1)
1
Installation manual
2
Operation manual
3
Unpacking instruction sheet
4
Wiring diagram
5
User interface kit (remote controller, 4 fixing screws, 2 plugs)
6
Screws (2x top plate fixing screws + 2x sound bottom plate
fixing screws + 4x lifting plate screws)
7
Clamp
8
O-ring (spare part)
9
Grommet (small)
10
Grommet (large)
11
Top plate insulation
12
Lifting plate (for lifting the unit)
13
Flexible water outlet piping
14
Flexible water inlet piping (with manometer)
O
VERVIEW OF THE INDOOR UNIT

Main components

2 18
17
19
3
Installation manual
7
24
20
1
16 15
13
7
8
21 10
2 2
23 23
14
4
2
22
4
6
5
12
11
1.
Air purge valve
Remaining air in the water circuit will be automatically removed
via the air purge valve.
2.
Temperature sensors (thermistors)
Temperature sensors determine the water and refrigerant
temperature at various points in the circuit.
3.
Switch box
The switch box contains the main electronic and electrical parts
of the indoor unit.
4.
Heat exchangers
5.
Refrigerant liquid connection R410A
6.
Refrigerant gas connection R410A
7.
Shut-off valves
The shut-off valves on the water inlet connection and water
outlet connection allow isolation of the indoor unit water circuit
side from the residential water circuit side. This facilitates
draining and filter cleaning of the indoor unit.
8.
Water inlet connection
9.
Water outlet connection
10. Drain valve
11. Water filter
The water filter removes dirt from the water to prevent damage
to the pump or blockage of the heat exchanger. The water filter
must be cleaned on a regular base. See
on page
34.
12. Expansion vessel (12 l)
13. Manometer
The manometer allows readout of the water pressure in the
water circuit.
14. Pump
The pump circulates the water in the water circuit.
15. Pressure relief valve
The pressure relief valve prevents excessive water pressure in
the water circuit by opening at 3 bar and discharging some
water.
16. Service ports R134a
17. Compressor
18. Accumulator
19. 3-way valve (option) (delivered with the EKHTS* domestic hot
water tank)
The motorized 3-way valve controls whether the water outlet is
used for space heating or the domestic hot water tank.
20. 4-way valve
21. 2-way valve
22. Thermal cut-out
23. Electronic expansion valve
24. T-piece (option) (delivered with the EKHTS* domestic hot water
tank)
7
9
"Maintenance activities"
EKHBRD011~016ABV1+Y1
Indoor unit for air to water heat pump system
4PW60970-1B

Advertisement