HARDWIRING THE INPUT TERMINALS
SAFETY PRECAUTIONS
CAUTION! Input circuit breaker must be "OFF" during the building installation.
CAUTION! Only qualified maintenance personnel should perform this task.
CHECK WIRING
Check wiring dimensions with the following table.
2
Step-Down and Isolation Transformers with hardwire
Wiring AWG
Wiring mm
2
OL6KRT2UTFHWIO / OL6KRT2UTFHWIOR
10 AWG
5.5 mm
2
OL10KRT2UTFHWIO / OL10KRT2UTFHWIOR
6 AWG
14.0 mm
Step 1: Separate the top and bottom covers
Loosen the four screws to separate the top and bottom covers.
Step 2: Fix the bottom cover on the terminal block
Tighten the two screws to fix the bottom cover on the terminal block.