Tyco ESFR-17 Manual

Tyco ESFR-17 Manual

Early suppression, fast response pendent sprinklers 16.8 k-factor
Hide thumbs Also See for ESFR-17:

Advertisement

Quick Links

Model ESFR-17
Early Suppression, Fast Response
Pendent Sprinklers 16.8 K-factor (For Europe Only)

IMPORTANT

Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
Installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/model-
esfr-17-early-sup-fast-res-pen-16_8
General
Description
The TYCO Model ESFR-17 Pendent
Sprinklers are Early Suppression, Fast
Response (ESFR) sprinklers with a
nominal K-factor of 16.8. The sprinkler
assembly is shown in Figure 1. They are
suppression mode sprinklers that are
especially advantageous as a means
of eliminating in-rack sprinklers when
protecting high-piled storage.
Model ESFR-17 Pendent Sprinklers are
primarily used for ceiling-only sprinkler
protection of, but not limited to, the fol-
lowing storage applications:
Page 1 of 4
• Most encapsulated or non-encap-
sulated common materials including
cartoned, unexpanded plastics
• Cartoned, expanded plastics
• Uncartoned, unexpanded plastics
• Uncartoned, expanded plastics
• Some storage arrangements of rub-
ber tires, roll paper, and aerosols
For more specific criteria, see Table A
and the applicable design standard.
The Model ESFR-17 Pendent Sprin-
klers provide the system designer
with hydraulic and sprinkler place-
ment options not presently available
to traditional ESFR Sprinklers having
a nominal K-factor of 14.0. In particu-
lar, Model ESFR-17 Pendent Sprinklers
are designed to operate at substan-
tially lower-end head pressures, as
compared to ESFR Sprinklers having
a nominal K-factor of 14.0. This feature
offers flexibility when sizing system
piping, as well as possibly reducing or
eliminating the need for a system fire
pump.

NOTICE

The Model ESFR-17 Pendent Sprinklers
described herein must be installed
and maintained in compliance with
this document, as well as with the
applicable standards recognized by
the Approval agency, in addition to
the standards of any authorities having
jurisdiction, such as FM Global. Failure
to do so may impair the performance
of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
In all cases, the appropriate NFPA or
FM installation standard, or other appli-
cable standard, must be referenced
to ensure applicability and to obtain
complete installation guidelines. The
general guidelines in this data sheet
are not intended to provide complete
installation criteria.
APRIL 2022
Worldwide
www.tyco-fire.com
Contacts
Sprinkler
Identification
Number (SIN)
See Table A
Technical
Data

Approvals

FM Approved
VdS Approved
LPCB Approved (094b and 007l)
NYC under MEA 356-01-E
EAC Approved

Finish

Natural Brass

Physical Characteristics

Frame . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Deflector . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze
Compression Screw . . . . . . . . . . Stainless Steel
Hook . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Strut. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Monel
Link Assembly . . . . . . . . . . . . . . . . Solder, Nickel
Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Brass
Sealing Assembly . . Beryllium Nickelw/TEFLON
Ejection Spring . . . . . . . . . . . . . . . . . . . . Inconel
Deflector Nut . . . . . . . . . . . . . . . . . . . . . . . .Brass

Additional Technical Data

See Table A
TFP315

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ESFR-17 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco ESFR-17

  • Page 1 For more specific criteria, see Table A ponents. Improper handling and and the applicable design standard. installation can permanently damage The Model ESFR-17 Pendent Sprin- a sprinkler system or its compo- klers provide the system designer nents and cause the sprinkler to fail...
  • Page 2 WRENCH Assembly FLATS Ejection Spring TEMPERATURE RATING 1-7/8" (47,6 mm) FIGURE 1 MODEL ESFR-17 EARLY SUPPRESSION, FAST RESPONSE PENDENT SPRINKLER, 16.8 K-FACTOR Operation Item Description The fusible link assembly is com- Sprinkler Identification Number (SIN) TY7226 prised of two link halves that are joined together by a thin layer of solder.
  • Page 3 N/A – Not Applicable TABLE B Step 1. Install the Model ESFR-17 MODEL ESFR-17 PENDENT SPRINKLERS Pendent Sprinkler in the pendent posi- COMMODITY SELECTION AND DESIGN CRITERIA OVERVIEW tion, see Figure 2.
  • Page 4 Care and Limited Ordering Maintenance Warranty Procedure The TYCO Model ESFR-17 Sprinklers For warranty terms and conditions, visit Contact your local distributor for avail- must be maintained and serviced in www.tyco-fire.com. ability. When placing an order, indicate accordance with this section.