Tyco ESFR-17 Manual

Tyco ESFR-17 Manual

Early suppression fast response pendent sprinklers 16.8 k-factor
Hide thumbs Also See for ESFR-17:

Advertisement

Quick Links

>
Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model ESFR-17
Early Suppression Fast Response Pendent Sprinklers
16.8 K-factor
General
Description
The Model ESFR-17 Pendent Sprin-
klers (Ref. Figure 1) are "Early Sup-
pression Fast Response Sprinklers"
having a nominal K-factor of 16.8. They
are suppression mode sprinklers that
are especially advantageous as a
means of eliminating in-rack sprin-
klers, when protecting rack storage.
The Model ESFR-17 is primarily de-
signed for use in ceiling only sprinkler
systems (i.e. no in-rack sprinklers) for
the protection of storage heights of
most encapsulated or non-encapsu-
lated common materials including car-
toned unexpanded plastics of up to 35
ft. (10,7 m) with ceiling heights to 40 ft.
(12,2 m), as well as cartoned ex-
panded plastics up to 25 ft. (7,6 m) with
ceiling heights to 30 ft.(9,1 m). In addi-
tion, the protection of some storage
arrangements of rubber tires, roll pa-
per, and aerosols can be considered.
In some cases, the Model ESFR-17
can be used to protect storage heights
up to 40 ft. (12,2 m) with ceiling heights
to 45 ft. (13,7 m) in combination with
one level of in-rack sprinklers.
The ESFR-17 provides the system de-
signer with hydraulic options not pres-
ently available to traditional ESFR
sprinklers having a nominal K-Factor
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 8
of 14.0. In particular, the Model ESFR-
17 has been designed to operate at
substantially lower end head pres-
sures, as compared to ESFR sprin-
klers having a nominal K-Factor of
14.0. This feature offers flexibility when
sizing the system piping, as well as
possibly reducing or eliminating the
need for a system fire pump.
WARNINGS
The Model ESFR-17 Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction (e.g., FM Global). Fail-
ure to do so may impair the perform-
ance of these devices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Sprinkler
Identification
Numbers
SIN TY7226 - (Pendent K=16.8)
JANUARY, 2005
Close
TFP315

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ESFR-17 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Tyco ESFR-17

  • Page 1 The Model ESFR-17 is primarily de- document, as well as with the applica- signed for use in ceiling only sprinkler ble standards of the National Fire Pro- systems (i.e.
  • Page 2: Technical Data

    8-Sealing Assembly ELEMENT 9-Ejection Spring WRENCH FLATS TEMPERATURE RATING 1-7/8" (47,6 mm) FIGURE 1, MODEL ESFR-17 EARLY SUPPRESSION FAST RESPONSE PENDENT SPRINKLER guidelines are not intended to provide Technical Design Criteria complete installation criteria. Data GENERAL GUIDELINES NOTE The National Fire Protection Associa- System Type: Wet pipe system.
  • Page 3 FM 2-2 — Deflector To Ceiling FM 2-2 — Thermal Sensing Element Distance: Distance: To Ceiling Distance: ESFR-17 (K=16.8) Pendent: ESFR-17 (K=16.8) Pendent: ESFR-17 (K=16.8) Pendent: 6 to 14 inches (152 to 356 mm). 5 to 14 inches (121 to 356 mm).
  • Page 4 Maximum Maximum Minimum Flow Pressure, PSI (BAR) Building Storage Comparison to Other TFP ESFR Sprinklers Height, Height, Feet Feet ESFR-1 ESFR-17 ESFR-25 ESFR-17 PENDENT UPRIGHT PENDENT PENDENT K = 14.0 K = 16.8 K = 25.2 K = 16.8 See Data Sheet...
  • Page 5 Maximum Maximum Minimum Flow Pressure, PSI (BAR) Building Storage Comparison to Other TFP ESFR Sprinklers Height, Height, Feet Feet ESFR-1 ESFR-17 ESFR-25 ESFR-17 PENDENT UPRIGHT PENDENT PENDENT K = 14.0 K = 16.8 K = 25.2 K = 16.8 See Data Sheet...
  • Page 6 Maximum Minimum Flow Pressure, PSI (BAR) Arrangement Building Storage Comparison to Other TFP ESFR Sprinklers Height, Height, Feet Feet ESFR-1 ESFR-17 ESFR-25 ESFR-17 PENDENT UPRIGHT PENDENT PENDENT K = 14.0 K = 16.8 K = 25.2 K = 16.8 See Data Sheet...
  • Page 7: Operation

    The fusible link assembly is comprised impairment of the sprinkler. of two link halves that are joined to- Step 1. The ESFR-17 Pendent Sprin- gether by a thin layer of solder. When kler must be installed in the pendent the rated temperature is reached, the position.
  • Page 8: Care And Maintenance