Accuracy at Reference Conditions
Parameter
Voltage
Rogowski Mode
Direct Input
Clamp Mode
1500 A iFlex
3000 A iFlex
6000 A iFlex
40 A
Frequency
Aux Input
Voltage Min/Max
Current Min/Max
THD on Voltage
THD on Current
Power Factor
Cosφ/DPF
Range
1000 V
0.1 V
15 mV
0.01 mV
150 mV
0.1 mV
50 mV
0.01 mV
500 mV
0.1 mV
150 A
0.1 A
1500 A
1 A
300 A
1 A
3000 A
10 A
600 A
1 A
6000 A
10 A
4 A
1 mA
40 A
10 mA
42.5 Hz to 69 Hz
0.01 Hz
±10 Vdc
0.01 V
1000 V
0.1 V
defined by accessory
defined by accessory
1000 %
0.1 %
1000 %
0.1 %
0.01
0 ≤PF ≤1
0.01
0 ≤Cosφ ≤1
Intrinsic Accuracy at Reference Conditions
Resolution
(% of Reading + % of Range)
±(0.2 % of rdg. + 0.01%)
±(0.3 % + 0.02 %)
±(0.3 % + 0.02 %)
±(0.2 % + 0.02 %)
±(0.2 % + 0.02 %)
±(1 % + 0.02 %)
±(1 % + 0.02 %)
±(1 % + 0.03 %)
±(1 % + 0.03 %)
±(1.5 % + 0.03 %)
±(1.5 % + 0.03 %)
±(0.7 % + 0.02 %)
±(0.7 % + 0.02 %)
±0.1 %
±(0.2 % + 0.02 %)
±(1 % + 0.1 %)
±(5 % + 0.2 %)
±(2.5 % + 0.05 %)
±(2.5 % + 0.05 %)
±0.025
±0.025