Input Shift
Scb
PV input filter
FILt
Selection of power
frequency and
Fru
temperature scale
Low limit of SV
SPL
Upper limit of SV
SPH
Parameter Scb is used to make input shift to
compensate the error produced by sensor or input
signal itself.
PV-after-compensation=
PV-before-compensation + Scb.
The value of FILt will determine the ability of
filtering noise.
When a large value is set, the measurement input
is stabilized but the response speed is slow.
Generally, if great interference exists, then you
can increase parameter "FILt" gradually to make
momentary fluctuation of measured value less
than 2 to 5.
When the meter of the instrument is being
examined at laboratory, "FILt" should be set to 0
or 1 to short the response time.
50C: 50Hz, ℃
50F: 50Hz, ℉
60C: 60Hz, ℃
60F: 60Hz, ℉
6
-199~
0
+400
0~40
1
50C, 50F,
50C
60C, 60F
-999~
0
3000
-999~
400
3000