Flow Rates; Installation - Xylem FS-5 Installation & Maintenance Instructions Manual

General purpose liquid flow switch
Table of Contents

Advertisement

FLOW RATES

Flow rates required to activate flow switch are shown
in chart below. The values are calculated for sensing
water (potable, non-polluted) in a horizontal pipe.
Flow Rates
Pipe
Size NPT
in. (mm)
Settings
gpm (lpm)
Factory or
3
(20)
4
or
Minimum
1
(25)
Maximum
Values are ± 10%
INSTALLATION –
STEP 1 - Determine the Location of the Flow Switch
• The flow switch should be located in a horizontal
section of pipe where there is a straight horizontal run
of at least 5 pipe diameters on each side of the flow
switch.
• The flow switch must be installed in the upright
position as shown with arrow mark on side of casting
in the same direction as fluid will flow.
• Some system conditions that require more than 5 pipe
diameters are high viscosity fluid and high fluid velocity.
• The flow switch should be installed in the pump suction
piping when spring-loaded check valves and/or other
close coupled accessories are installed in the pump
discharge piping.
Mode of Operation
Max. Flow
Rate gpm
Flow
No Flow
(lpm) w/o
gpm (lpm)
Paddle Damage
1.5
(5.7)
1.1
(4.2)
16.62 (63)
15 (56.8)
10 (37.9)
Settings will vary when used to sense flow of other
fluids.
NOTE: DO NOT USE LIQUID FLOW
27 (102)
3/4" or 1"
PIPE
Fluid Flow
MINIMUM
SWITCHES ON SYSTEMS WITH
FLOW VELOCITY GREATER THAN
10 FEET (3M) PER SECOND.
5 x D
MINIMUM
D= PIPE DIAMETER
D
5 x D
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fs5-j-3-eFs5-j-4-eFs5-s-1Fs5-ds-1Fs5-d-3Fs5-d-4 ... Show all

Table of Contents