Fujitsu ARXG22KMLB Design & Technical Manual page 422

Hide thumbs Also See for ARXG22KMLB:
Table of Contents

Advertisement

Model: AUXG22KVLA
Outdoor temperature
(°CDB)
-15.0
-10.0
-5.0
0.0
5.0
7.0
10.0
15.0
20.0
24.0
NOTES:
• TC: Total Capacity (kW)
• Values mentioned in the table are based on the following conditions:
– Pipe length: 5 m, Height difference: 0 m (Outdoor unit—Indoor unit)
6-3. Heating capacity
16.0
(°CWB)
TC
-16.0
5.55
-11.0
6.44
-7.0
6.80
-2.0
7.78
3.0
8.95
6.0
8.95
8.0
8.95
10.0
8.95
15.0
8.95
18.0
8.95
Indoor temperature (°CDB)
18.0
20.0
TC
TC
5.41
5.28
6.29
6.13
6.64
6.48
7.60
7.41
8.73
8.52
8.73
8.52
8.73
8.52
8.73
8.52
8.73
8.52
8.73
8.52
- 414 -
22.0
24.0
TC
TC
5.15
5.02
5.98
5.83
6.31
6.15
7.23
7.04
8.31
8.09
8.31
8.09
8.31
8.09
8.31
8.09
8.31
8.09
8.31
8.09
6. Capacity table