Fujitsu ARXG22KMLB Design & Technical Manual page 231

Hide thumbs Also See for ARXG22KMLB:
Table of Contents

Advertisement

¢ Specifications
Dimensions and other specifications on the wired remote controller are as follows.
Model name
Display
Dimensions (H × W × D)
Weight
Input voltage
Power consumption
Usage temperature range
Usage humidity range
Storage temperature range
Storage humidity range
 Wiring specifications
Use
Remote controller cable
¢ Installation
Connect the end of remote controller cable directly to the exclusive terminal block.
Functional earthing
(If necessary)
Remote controller cable
(Non-polar)
NOTES:
• Layout of terminal block and PCB is varies depending on the type of indoor unit.
• Operation may fail if it is connected to the outdoor unit or the terminal block for power sup-
ply.
13-9. Wired remote controller (UTY-RNRYZ*: Optional part)
120
UTY-RNRYZ*
3.8-inch FSTN LCD (255 × 160 dots) with touch panel
mm
g
V
W
°C
%
°C
%
Cable size
Non-polar 2-core,
2
0.33 to 1.25 mm
Terminal block
- 223 -
[Unit : mm]
20.4
120 × 120 × 20.4
220
DC 12
Max. 0.3
0 to 40
20 to 90 (no condensation)
-10 to 60
20 to 90 (no condensation)
Wire type
Use sheathed PVC cable.
Twisted pair
Indoor unit PCB
Remarks
13. Remote controller