Jack Jumper™ Cutout Bypass Tool
DANGER
!
Contact with high voltage will cause death or grievous personal
injury to the operator. Only use this device in conjunction with
safe operating practices around energized lines and equipment.
Product Description
The Jack Jumper™ Cutout Bypass Tool permits a safe and quick method to bypass an overhead
cutout without the tedious use of bulky jumper cables. The tool is indispensable for fuse
coordination tasks and permits easy bypass of an underground dip. The Jack Jumper™ Cutout
Bypass Tool saves time and money, eliminates risk of service interruption and prevents accidental
cross phasing.
The primary purpose of the Jack Jumper™ Cutout Bypass Tool is to provide temporary fuse
replacement when performing fuse coordination on cutouts. The Jack Jumper™ Cutout Bypass
Tool is rated at 100 Amps continuous on AC current without exceeding a 40°C temperature rise. It
is used to bypass cutouts on both overhead lines and underground taps. For 200 Ampere SMD-20
systems attach two Jack Jumper™ Cutout Bypass Tools on opposite sides of the SMD-20 Power
Fuse (this only works for SMD-20 Power Fuse Tools and cannot be utilized for standard cutouts).
Installation and removal of the Jack Jumper™ Cutout Bypass Tool is done with a shotgun stick.
WARNING
!
Follow safe work procedures and practices when utilizing this
device. Failure to use this device in a safe manner can result
in death, grievous personal injury and or equipment damage.
WARNING
!
Only trained and qualified personnel should operate, inspect
and maintain this device.
WARNING
!
Only install the Jack Jumper™ Cutout Bypass Tool with the use
of an insulated shotgun stick. When attaching or detaching the
Jack Jumper™ Cutout Bypass Tool do not use abrupt or rough
movements, be gentle and do not hurry.
Top Perpendicular
Phone
(828)323-8914
Fax
(828)323-8410
sales@utilitysolutionsinc.com
Email
www.utilitysolutionsinc.com
Web
101 33
Street Drive SE · Hickory, NC 28602
rd
USJJ-005 38 kV Cutout Bypass Tool &
15 kV SMD-20 Power Fuse Bypass Tool
Ring
Spring
Mechanism
Bottom In-Line
Ring
C-00829 USJJ-005 Instruction Manual (6-4-15)
!
!
Carefully read and fully understand the INSTRUCTION
MANUAL prior to operating, maintaining or testing this
device. Improper operation, handling or maintenance of this
device can result in death, grievous personal injury and or
equipment damage.
!
!
These instructions are not intended to replace or be a substitute
for proper safety training procedures. Failure to select the
proper tool in regards to minimum system requirements can
result in death, grievous personal injury and or equipment
damage.
!
!
Never install or remove Jack Jumper™ Cutout Bypass Tool
without a working fuse in place. It is not a switch and should
never be used as one.
!
!
If you are servicing a fuse, replace the fuse as quickly as possible.
The fuse is a protective device. The Jack Jumper™ Cutout Bypass
Tool DOES NOT FUNCTION AS A FUSE. If you must leave
the area, replace any fuses and remove the Jack Jumper™ Cutout
Bypass Tool. It is not a fuse replacement or permanent by-
pass mechanism.
Attachment Hook
WARNING
WARNING
WARNING
WARNING
Upper
Lower
Attachment Hook
!
!
!
!

Advertisement

loading

Summary of Contents for Utility Solutions Jack Jumper USJJ-005

  • Page 1 Jack Jumper™ Cutout Bypass Tool C-00829 USJJ-005 Instruction Manual (6-4-15) USJJ-005 38 kV Cutout Bypass Tool & 15 kV SMD-20 Power Fuse Bypass Tool DANGER WARNING Carefully read and fully understand the INSTRUCTION MANUAL prior to operating, maintaining or testing this Contact with high voltage will cause death or grievous personal device.
  • Page 2 If the Jack Jumper™ Cutout Bypass Tool appears to be malfunctioning do not attempt to repair it. Immediately remove it from service, tag it as defective, note the specific problem, and return it to Utility Solutions for inspection. Any disassembly will invalidate any and all product guarantees, claims and warranties.