Step 8 Connecting Up And Removing Air In The Circuit - Samsung AJ100RCJ5EG Installation Manual

Table of Contents

Advertisement

• Make sure that the spaces where the refrigerant
pipes are installed comply with national gas
regulations.
• Be sure to perform works such as additional
refrigerant charging and pipe welding under the
conditions of good ventilation.
• Be sure to perform welding and piping works for
mechanical connections under the conditions that
the refrigerant does not circulate.
• When reconnecting the pipes, make sure to perform
flared-jointing newly to prevent refrigerant leakage.
• When working on the refrigerant pipes and the
flexible refrigerant connectors, be careful that they
are not damaged physically by surrounding objects.
• For installation with handling the R-32 refrigerant,
use the special tools for the R32 refrigerant (manifold
gauge, vacuum pump, charging hose, etc.).
• During tests never pressurize the appliances with
a pressure higher than the maximum allowable
pressure(as indicated on the nameplate of the unit).
• Never directly touch any accidental leaking
refrigerant. This could result in severe wounds
caused by frostbite.
• Never install a dryer to this unit in order to guarantee
its lifetime.
• If the pipes require brazing ensure that OFN(Oxygen
Free Nitrogen) is flowing through the system.
• Nitrogen blowing pressure range is 0.02 to 0.05 MPa.
• If you need a pipe longer than specified in piping
codes and standards, you must add refrigerant to the
pipe. Otherwise, the indoor unit may freeze.
• While removing burrs, put the pipe face down to
make sure that the burrs do not get in to the pipe.
Step 8 Connecting up and removing air
in the circuit
WARNING
• When installing, make sure there is no leakage. When
recovering the refrigerant, ground the compressor
first before removing the connection pipe. If the
refrigerant pipe is not properly connected and the
compressor works with the service valve open, the
pipe inhales the air and it makes the pressure inside
of the refrigerant cycle abnormally high. It may cause
explosion and injury.
The outdoor unit is loaded with sufficient R-32
refrigerant.Do not vent R-32 into atmosphere: it is a
fluorinated greenhouse gas, covered by Kyoto Protocol,
with a Global Warming Potential (GWP) = 675.
You should purge the air in the indoor unit and in the
pipe. If air remains in the refrigerant pipes, it affects the
compressor. It may cause reduction of cooling capacity
and malfunction. Refrigerant for air purging is not
charged in the outdoor unit. Use Vacuum Pump as seen
in the picture.
1 Check the piping connections.
2 Connect the charging hose of low pressure side of
manifold gauge to the packed valve having a service
port.
Model Name
AJ100RCJ5EG
• If the valve diameter of indoor and outdoor unit
are different, please use Tube-connector.
Valve
3/8''
1/2''
2
3
English
21