Installation Places; Select The Best Location - LG UM60F Instruction Manual

Hide thumbs Also See for UM60F:
Table of Contents

Advertisement

INSTALLATION PLACES

Select the best Location

[Ceiling Concealed Duct]
- The place shall easily bear a load exceeding four times the indoor unit's weight.
- The place shall be able to inspect the unit as the figure.
- The place where the unit shall be leveled.
- The place shall allow easy water drainage.
(Suitable dimension "H" is necessary to get a slope to drain as figure.)
- The place shall easily connect with the outdoor unit.
- The place where the unit is not affected by an electrical noise.
- The place where air circulation in the room will be good .
- There should not be any heat source or steam near the unit.
Ceiling Concealed Duct – Low Static
Inspection hole (600 x 600)
Top view
(unit: mm)
600
or More
Side view
(unit: mm)
• Suitable dimension "H" is necessary to get a slope
to drain as shown in the figure
CAUTION
!
• In case that the unit is installed near the sea, the installation parts may be corroded by salt,
The installation parts (and the unit) should be taken appropriate anti-corrosion measures.
Inspection Hole Standard
Number of
Inspection hole
False ceiling & Actual ceiling
1
2
Hole size should be
more than the size
of IDU.
Control box
600
Air outlet
or More
Air outlet
H
= 20 or More
Distance between
More than 100 cm
20 cm to 100 cm
Less than 20 cm
INSTALLATION PLACES
Ceiling Concealed Duct – Mid Static
Top view
(unit: mm)
600
or More
Front view
Remarks
Sufficient space in the ceiling for servicing.
Insufficient space. Difficult for servicing
Minimum height for motor replacement.
17
Inspection hole
(600 x 600)
Control box
1 000
600
or More
or More
Front
H
= 20 or More