Mitsubishi Electric LGH-250RVXT-E Handbook page 50

Lossnay energy recovery ventilator
Table of Contents

Advertisement

Step
6
Function setting with PZ-61DR-E
When PZ-61DR-E is connected, according to the function status record data pre-
pared in Step 2, set the function settings with PZ-61DR-E.
If PZ-61DR-E is not connected, skip this step and proceed to Step 7.
To perform function settings with PZ-61DR-E, see the Lossnay technical manual or
remote controller manual.
The selection method for "M-NET address" on the function setting screen differs
between when the address setting switch on the Lossnay circuit board is set (the
address is other than "00") and when it is not set (the address is "00"). Check the ad-
dress setting of the replaced circuit board.
<When the address switch setting is other than "00">
For all function settings, always select the address of the Lossnay unit which the
circuit boards were replaced.
Even when there are multiple Lossnay units in the group, do not select "All".
<When the address switch is "00">
Always select "All".
Note:
When changing the settings of the function selection switches and address setting
switches on the circuit board after the functions were set with PZ-61DR-E, reset the
function settings according to "(10) Initialization" (page 50).
After resetting the function settings, perform the function settings again in the order
of Step 5 1 and Step 6.
If you change the M-NET address after the functions were set with PZ-61DR-E, the
settings with PZ-61DR-E will be reset. In this case, set the functions again with PZ-
61DR-E.
7
Restarting the system
Turn the power back on to the Lossnay unit which the circuit boards have been re-
placed, or when using M-NET, turn the power back on to the power supply unit con-
nected to the Lossnay unit.
In trial operation, make sure that the Lossnay unit with replaced circuit boards oper-
ates properly, and finish replacement work.
(10) Initialization
Set to initialize the remote controller PZ-61DR-E function setting.
All function settings which are changed by users are cancelled.
DIP-SW
SW No.
Setting
N/A
Setting
check
Function No.
-
-
-
-
Details
PZ-61DR-E
Setting Data
0
100
1
─ 50 ─
Check item
Address set-
ting
Function set-
ting
Trial opera-
tion
Setting
Initialization
check
N/A
Available

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lgh-200rvxt-eLgh-150rvxt-e

Table of Contents