Mitsubishi Electric Mr Slim PUHZ-RP50VHA4 Service Manual page 70

Split-type, heat pump air conditioners
Hide thumbs Also See for Mr Slim PUHZ-RP50VHA4:
Table of Contents

Advertisement

11-6. HOW TO CHECK THE PARTS
PUHZ-RP35/50/60/71VHA4
PUHZ-RP100/125/140VKA
PUHZ-RP100/125/140/200/250YKA
PUHZ-RP200YKAR1
Parts name
Thermistor (TH3)
<Liquid>
Disconnect the connector then measure the resistance with a tester.
Thermistor (TH4)
(At the ambient temperature 10 ~30 )
<Discharge>
Thermistor (TH6)
<Outdoor 2-phase pipe>
Thermistor (TH7)
<Ambient>
Thermistor (TH8)
<Heatsink>
Thermistor (TH32)
<Comp. surface>
Thermistor (TH33)
<Ref. check>
Fan motor(MF1,MF2)
Refer to next page.
Solenoid valve coil
Measure the resistance between the terminals with a tester.
(At the ambient temperature 20 )
<Four-way valve>
(21S4)
Motor for compressor
Measure the resistance between the terminals with a tester.
(Winding temperature 20 )
(MC)
U
V
W
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
(LEV-A/ LEV-B)
(Winding temperature 20 )
For RP35-RP71
Red
M
1
Brown
2
Blue
3
Orange
4
Yellow
5
White
6
Linear expansion valve
Disconnect the connector then measure the resistance with a tester.
(LEV-A/LEV-B/LEV-C)
(Winding temperature 20 )
For RP100-RP250
Gray
M
1
2
Orange
3
Red
4
Yellow
5
Black
6
OCH451D
Normal
TH4, TH32
160k ~410k
TH3
TH6
4.3k ~9.6k
TH7
TH33
TH8
39k ~105k
RP35-71
2350±170
Red - White
Red - Orange
Gray - Black
Gray - Red
Check points
Abnormal
Open or short
Normal
RP100-250
1435±150
Normal
Refer to 6-2.
Normal
Brown - Yellow
46±4
Normal
Gray - Yellow
46±3
70
Abnormal
Open or short
Abnormal
Open or short
Abnormal
Brown - Blue
Open or short
Abnormal
Gray - Orange
Open or short

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents