Standards, Certifications And Government Regulations - Brant Radiant Heaters DX3L Series Manual

Gas-fired infrared tube heater
Table of Contents

Advertisement

DX3L
Series

Standards, Certifications and Government Regulations

Installation of this tube heater must comply with all applicable local, state and national specifications,
regulations and building codes. Contact the local building inspector and/or fire marshall for guidance.
In the absence of local codes, the installation must conform to the latest edition of:
United States: National Fuel Gas Code, ANSI Z223.1 (NFPA 54).
Chart 2.1 •
Standards and Code Installation Guidelines
Building
Type
Installation of this tube heater in public garages must conform to the following codes:
Public
Garages
United States: Standard for Parking Structures NFPA 88A (latest edition) or the
Code for Motor Fuel Dispensing Facilities and Repair Garages NFPA 30A (latest
edition).
Canada: Refer to CAN/CGA B149.1-10: Installation Codes for Gas Burning Appliances
and applicable Standards for Public Garages.
Guidelines:
• Heaters must not be installed less than 8 ft. (2.4 m) above the floor. Minimum
clearances to combustibles must be maintained from vehicles parked below the
heater.
• When installed over hoists, minimum clearances to combustibles must be maintained
from the upper most point of objects on the hoist.
Aircraft
Installation of this tube heater in aircraft hangars must be in accordance with the
Hangars
following codes:
United States: Refer to Standard for Aircraft Hangars, ANSI/NFPA 409
(latest edition).
In Canada: Refer to Standard CAN/CGA B149.1-10 and applicable Standards for
Aircraft Hangars.
Guidelines:
• In aircraft storage and servicing areas, heaters shall be installed at least 10 ft. (3 m)
from above the upper surface of wings or of the engine enclosures of the highest
aircraft that may be housed in the hangar. The measurement shall be made from the
wing or engine enclosure, whichever is higher from the floor, to the bottom of the
heater.
• In areas adjoining the aircraft storage area (e.g., shops, offices) the bottom of heaters
shall be installed no less than 8 ft. (2.4 m) above the floor.
• Suspended or elevated heaters shall be located in spaces where they shall not be
subject to damage by aircraft, cranes, movable scaffolding or other objects.
Provisions shall be made to assure accessibility to suspended tube heaters for recurrent
maintenance purposes.
2.0
Canada: CAN/CGA B149.1-10, Canadian Electrical Code C22.1
Safety
Standards, Certifications and Government Regulations
Building Type
Codes and Guidelines
9

Advertisement

Table of Contents
loading