50 Kanalflakt Way, Bouctouche, NB, E4S 3M5 Tel.: 800.565.3548 • Fax: 877.747.8116 Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position.
Page 2
Your ventilation system should be installed in accordance with the local building code that is in effect, in absence of such requirements, it is recommenced to check with local authorities having jurisdiction in your area prior to installing this product fantech...
* ASHRAE 62.2-2016 Table 4.1, Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. Bathroom: If the ERV is going to provide the required local exhaust ventilation for each bathroom with each a continuous 20 CFM (10 L/s), this ventilation rate can be considered as part of the whole-building ventilation rate. fantech...
The ERV’s airflow must be balanced after installation using the procedure found in the section “AIRFLOW BALANCING” ERV ducting for fully Dedicated System Stale air from inside Fresh air from outside Fresh air to living areas Outside Stale air to outside fantech...
* Unit airflow should be balanced while ERV is on outside “Normal” speed and furnace blower is running. Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified 24 VAC Transformer installation, i.e.
“Normal” speed and furnace blower is running. Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified 24 VAC Transformer installation, i.e.
* Unit air flow should be balanced while ERV is on "Normal" speed and outside furnace blower is running. Fantech energy recovery ventilators (ERV) that use a supply fan shutdown for frost prevention do not include an outdoor air motorized damper. If you are using a simplified 24 VAC Transformer installation, i.e.
Pull the insulation procedure for both the supply insulated flexible duct. Cut a over the duct and pull the vapor and exhaust hoods. hole for both the intake and barrier over the sleeve. Secure exhaust hoods. with appropriate tape or sealant. fantech...
In this method, the exhaust air is not ducted back from bathrooms, kitchens, etc to the ERV with “dedicated lines”. As per building codes and installation requirements for combustion appliances: Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage. fantech...
4 corners of the unit unit is level. created in the chain. The and tighten. spring will then support the unit's weight and absorb vibrations. fantech...
Page 12
If outdoor air temperature is above 32°F (0°C) at the extract air (30% RH/72°F, 30% RH /22°C), no drain line installation is required. If this is the case keep the drain spout as shipped from factory with the cap. fantech...
The integrated dampers are preset at the fully opened position. In order to reduce the amount of airflow, turn the adjustable lever using a flat screw driver by turning it counter clock wise. Turning the lever clockwise may damage the plastic screw head. Follow the balancing steps to properly adjust the airflow. fantech...
STEP #3: Secure the adjustable arm by tightening the set screw as shown in Illustration #3. Illustration #1 Set screw (on top) Adjustment lever (in front) Illustration #2 Illustration #3 fantech...
• Up to 5 can be used in one system • Use in bathroom, kitchen, laundry room MDEH1 • Rotary dial Dehumidistat • Multiple units can be used • We recommend setting the relative humidity above 80% during the summer fantech...
Page 17
24-VOLT TERMINAL BLOCK COOLING SYSTEM WIRE As per building codes and installation requirements for combustion appliances: Air return ducts, or openings for air return, should not be placed in enclosed spaces containing combustion appliances that are subject to spillage. fantech...
A hole or tear in outer duct covering Tape any holes or tears made in the outer duct covering Ensure that the vapor barrier is completely sealed. Note: It is best to get the unit checked by a certified HVAC Contractor/Technician. fantech...
Lines beginning of the warranty period. Vacuum the Inside of the Annually • The fans found in all Fantech ERVs Unit require no lubrication, and are factory balanced to prevent vibration and Clean and Un-block Annually promote silent operation.
Rotate the core so that its other air inlet is facing down and repeat step 5. With plates still oriented vertically allow the core to dry, normally 2-3 hours. Slide back the core into the unit Replace both filters. fantech...
Parts list * If the first set of digits (can be between 7 and 10 VER200 BOM # Description digits long) of your serial number is # 1004482754 or (99286) lower, your replacement door kit is #427756. R2E190 Radical, Rep. Kit...