Fantech VHR 704 Installation Manual

Fantech VHR 704 Installation Manual

Heat recovery ventilator
Hide thumbs Also See for VHR 704:
Table of Contents

Advertisement

Available languages

Available languages

VHR 704
Heat Recovery Ventilator
Your ventilation system should be installed in conformance with the appropriate provincial requirements or, in the absence of
such requirements, with the current edition of the National Building Code, and / or ASHRAE's "Good Engineering Practices".
United States
10048 Industrial Blvd., Lenexa, KS, 66215
Tel.: 800.747.1762 • Fax: 800.487.9915
Canada
50 Kanalflakt Way, Bouctouche, NB, E4S 3M5
Tel.: 800.565.3548 • Fax: 877.747.8116
Fantech reserves the right to modify, at any time and without notice, any or all of its products' features, designs,
components and specifications to maintain their technological leadership position.
Please visit our website www.fantech.net for more detailed technical information.
Installation Manual
Item #: 403409
Rev Date: 2016-06-10

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VHR 704 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Fantech VHR 704

  • Page 1 50 Kanalflakt Way, Bouctouche, NB, E4S 3M5 Tel.: 800.565.3548 • Fax: 877.747.8116 Fantech reserves the right to modify, at any time and without notice, any or all of its products’ features, designs, components and specifications to maintain their technological leadership position.
  • Page 2 Note Warning/ Information Technical Practical tip Important information note PLEASE READ THIS MANUAL BEFORE INSTALLING UNIT For residential use only Before installation careful consideration must be given to how this system will operate if connected to any other piece of mechanical equipment, i.e. a forced air furnace or air handler operating at a higher static pressure.
  • Page 3: Table Of Contents

    Table of content DETERMINING YOUR AIRFLOW REQUIREMENT ........... . . 4 INSTALLATION EXAMPLES Fully dedicated system .
  • Page 4: Determining Your Airflow Requirement

    Determining your airflow requirement Room Count Method Room classification Number of rooms CFM (L/s) CFM Required Master bedroom x 10 L/s (20 CFM) if yes add 10 L/s (20 CFM) Basement yes or no if no = 0 Bedrooms x 5 L/s (10 CFM) Living room x 5 L/s (10 CFM) Others...
  • Page 5: Installation Examples

    Installation examples Suggested installation for: Example only – duct configuration may differ depending on the model. • Hydronic baseboard • Infloor heating FULLY DEDICATED SYSTEM • Electric baseboard BEST FOR NEW CONSTRUCTION • Mini split heat pump Benefits: Provides the best fresh air distribution in the Stale air is drawn from key areas of the home requiring local exhaust house;...
  • Page 6: Partially Dedicated System

    HRV is not operating. See wiring diagram (figure 1). *Transformer and Damper motor not included You may also choose to use a Fantech HRV that uses a recirculation defrost that incorpo- rates an outdoor air damper.
  • Page 7: Simplifed Installation Option 1

    Figure 1 return air duct that closes when the HRV is not operating. See wiring diagram (figure 1). You may also choose to use a Fantech HRV that uses a recirculation defrost that incorpo- *Transformer and Damper motor not included...
  • Page 8: Option 2

    Figure 1 return air duct that closes when the HRV is not operating. See wiring diagram (figure 1). You may also choose to use a Fantech HRV that uses a recirculation defrost that incorpo- *Transformer and Damper motor not included...
  • Page 9: Exterior Ducting Installation

    Exterior ducting installation Weatherhood location OUTSIDE CORNER INSIDE CORNER • Decide where your intake and exhaust hoods will be located. 36" (1m) 36” (1m) min. min. Locating the Intake Weatherhood • Should be located upstream (if there are prevailing winds) from the 6' (2m) exhaust outlet.
  • Page 10: Installing Ducts To / From Inside

    The stale air exhaust system is used to draw air from the points in the house where the worst air quality problems occur. Due to its lower capacity, the VHR 704 is designed to vent from a single source point only and to the bathroom that is closest to the unit or directly out of the furnace return.
  • Page 11: Ducting Installation Examples

    Ducting installation examples Fully dedicated system Partially dedicated system FEL 4 (4” Miter Elbow) Exhaust CG 4 (4” Adjustable Grill) Bedrooms Bathroom Central Control - optional Fresh air to living room Supply Supply Exhaust Exhaust Fresh Air 460 mm Exhaust Air 460 mm Simplified installation - Option 2 Simplified installation - Option 1...
  • Page 12: Hrv Installation

    HRV installation Location The HRV must be located in a conditioned space where it will be possible to conveniently service the unit. Typically the HRV would be located in the mechanical room or an area close to the outside wall where the weatherhoods will be mounted.
  • Page 13: Airflow Adjustment & Balancing

    Airflow adjustment & balancing Fantech's superior design and use of EBM Motors results in a steep fan curve that usually does not require balancing. Commissioning the system after installation is recommended which include confirming the proper operation of the system and how it interacts with other components within the home.
  • Page 14: Low Voltage Control

    Low voltage control systems * Please see instruction manuals for individual controls for proper wiring and set up of control systems. – CENTRAL CONTROLS These control options can only be used individually CONTROLS FEATURES CONNECT TO ECO-TOUCH ® • Our most complete, yet easy to use control system •...
  • Page 15: Electrical Connections

    Electrical connections...
  • Page 16 Electrical connections (cont'd) ELECTRICAL Standard Accessory Control Contact Standard Furnace Interlock Wiring CONNECTION TO FURNACE THERMOSTAT TERMINALS FOUR WIRE TWO WIRE heating only FOR A FURNACE CONNECTION TO A COOLING SYSTEM: FURNACE 24-VOLT On some older thermostats, energizing TERMINAL BLOCK COOLING SYSTEM the R and G terminals at the furnace WIRE...
  • Page 17: Troubleshooting

    Troubleshooting Problem Causes Solutions Air is too dry Dehumidistat control is set too low Increase the desired level of humidity. Change ventilation mode from continuous mode to standby. HRV out of balance Have contractor balance HRV airflows Air is too humid Dehumidistat control is set too high Reduce the desired level of humidity.
  • Page 18: Hrv Maintenance Chart

    Lines beginning of the warranty period. Vacuum the Inside of the Annually • The fans found in all Fantech HRVs Unit require no lubrication, and are factory balanced to prevent vibration and Clean and Un-block Annually promote silent operation.
  • Page 19 Notes...
  • Page 20 NOTES...
  • Page 21 50 Kanalflakt Way, Bouctouche, NB, E4S 3M5 Tel.: 800.565.3548 • Fax: 877.747.8116 Fantech se réserve le droit de modifier partiellement ou entièrement, en tout moment et sans préavis, les caractéristiques, la conception, les composantes et les spécifications de ses produits, afin de conserver sa position de leader de technologie.
  • Page 22 Note Avertissement/ Information Information Conseil Note importante technique pratique VEUILLEZ LIRE LE MANUEL AVANT D’INSTALLER L’APPAREIL À fin d’installation résidentielle seulement Avant de procéder à l’installation, examinez avec soin la façon dont le système fonctionnera s’il est relié à tout autre appareil mécanique, notamment une fournaise à...
  • Page 23 Table des matières DÉTERMINER VOS BESOINS DE VENTILATION ........... . . 24 EXEMPLES D'INSTALLATION Système entièrement spécialisé...
  • Page 24: Déterminer Vos Besoins De Ventilation

    Déterminer vos besoins de ventilation Méthode compte de pièces Pi 3 /min (L/s) Liste des pièces Nombre de pièces PCM Requis x 10 L/s (20 pi 3 /min) Chambre principale 3 /min Si oui, ajoutez 10 L/s (20 pi Sous-sol oui ou no Sinon = 0 x 5 L/s (10 pi 3 /min)
  • Page 25: Exemples D'installation

    Exemples d'installation Installation suggérée pour: • Plinthe à eau chaude Exemple seulement – la configuration des conduits peut être différente selon le modèle. • Plancher chauffant • Plinthe électriques SYSTÈME ENTIÈREMENT SPÉCIALISÉ • Thermopompe mural bibloc (NOUVELLE CONSTRUCTION) Avantages: Fourni la meilleure répartition de l’air frais dans la maison;...
  • Page 26: Système Partiellement Spécialisé

    VRC ne fonctionne pas. Voir le schéma de câblage (figure 1). Vous pouvez aussi choisir d'utiliser une VRC Fantech qui utilise un dégivrage de recirculation qui intègre un volet d'air extérieur.
  • Page 27: Installation Simplifiée

    VRC ne fonctionne pas. Voir le schéma de câblage (figure 1). Vous pouvez aussi choisir d'utiliser une VRC Fantech qui utilise un dégivrage de recirculation qui intègre un volet d'air extérieur.
  • Page 28: Option 2

    VRC ne fonctionne pas. Voir le schéma de câblage (figure 1). Vous pouvez aussi choisir d'utiliser une VRC Fantech qui utilise un dégivrage de recirculation qui intègre un volet d'air extérieur.
  • Page 29: Installation Des Conduits Extérieurs

    Installation des conduits extérieurs Emplacement des hottes Coin extéreur Coin intérieur OUTSIDE CORNER INSIDE CORNER • Décidez de l’emplacement des hottes d’aspiration et d’évacuation. 36po (1m) 36po (1m) 36" (1m) 36” (1m) min. min. Emplacement de la hotte d’aspiration • Doit être située en amont de la sortie d’évacuation (en présence de vents dominant).
  • Page 30: Installation Des Conduits Intérieurs

    Il est possible de puiser à même d'autres points sources s'ils sont bien conçus ou s'ils sont installés sur un nécessaire d'évacuation pour salle de bains Fantech distinct afin de ventiler d'autres pièces. Les nécessaires d'évacuation pour salle de bains Fantech sont énumérés ci-après...
  • Page 31: Exemple D'installation Des Consuits

    Exemples d'installation des conduits Système entièrement spécialisé Système partiellement spécialisé FEL 4 (Coude 4 po) FEL 4 (Coude 4 po) Grille d'évacuation CG4 (Grille ajustable 4 po) Grille d'évacuation CG4 (Grille ajustable 4 po) Commande centrale (en option) Chambres Salle de bains Salle de bains Chambres Commande centrale (en option)
  • Page 32: Installation Du Vrc

    Installation du VRC Emplacement Le VRC doit être situé dans un endroit chauffé où il sera possible d’en effectuer l'entretient convenablement. Généralement, le VRC doit être situé dans la chambre des appareils mécaniques ou à proximité. S’il n’y a pas de sous-sol ou si le sous-sol ne convient pas, il est possible d’installer l’appareil dans la lingerie ou dans la buanderie.
  • Page 33: Équilibrage Du Débit D'air

    Équilibrage du débit d'air Grâce à la conception supérieure des produits de Fantech et à l'utilisation de moteurs EBM, l'inclinaison des pâles très prononcée résultante signifie qu'il n'est pas nécessaire d'équilibrer le débit d'air. Il est recommandé de mettre l'appareil en service après l'installation pour vérifier son fonctionnement et évaluer son interaction avec les autres appareils de la maison.
  • Page 34: Système De Contrôle À Basse Tension

    Système de contrôle à basse tension * Veuillez voir les instructions individuelles des contrôles pour le câblage et la mise en pièce appropriée. – CONTRÔLES CENTRALS Ces options de contrôle peuvent seulement être utilisé individuellement CONTRÔLE CARACTÉRISTIQUES CONNEXION À ECO-TOUCH ® •...
  • Page 35: Schémas Électriques

    Schémas électroniques...
  • Page 36 Schémas électroniques (suite) CONNEXION ÉLECTRIQUE Câblage de verrouillage de la fournaise standard Contact de commande des accessoires standard À UNE FOURNAISE BORNES DU THERMOSTAT QUATRE FIL DEUX FILS chauffage seulement CARTE ÉLECTRONIQUE DU VRC DANS LE CAS D’UNE FOURNAISE RACCORDÉE À...
  • Page 37: Dépannage

    Dépannage Problème Causes Solutions L’air est trop sec – Le déshumidistat est réglé trop bas – Augmentez le niveau voulu d’humidité. Faites passer le mode de ventilation de « continu » à « attente ». – Le VRC est déséquilibré –...
  • Page 38: Tableau D'entretien

    à proximité du domicile de l'acheteur ou dans sa région. • Fantech se réserve le droit de fournir des pièces remises à neuf comme pièces de rechange. • Les frais de transport, de retrait et d'installation sont assumés par...
  • Page 39: Parts List

    Parts list • Liste des composantes VHR704 BOM # Description (40392) Motor, R2E 133-BH94-18 404378 Electrostatic Filters Kit 8” x 8.3” 405116 Heat Recovery Cell 8.5” x 8.5” x 8” 404350 Wing Screw 10-32 412070 Capacitors 2uF 412315 PCB, UNICTRL 402004 Door Switch 410867...
  • Page 40 Fantech reserves the right to make technical changes. Fantech se réserve le droit de faire des changements tech- For updated documentation please refer to www.fantech.net niques. Pour de la documentation à jour, s'il vous plaît se référer au www.fantech.net Fantech®...