Reheat Mode; Scheduled Mode - Daikin Altherma EHBH04CBV User Reference Manual

Low temperature split
Hide thumbs Also See for Altherma EHBH04CBV:
Table of Contents

Advertisement

CAUTION
The booster heater permission schedule is used to restrict
or allow anti-legionella heater operation based on a weekly
program.
Advice:
In
disinfection function, at least allow the anti-legionella
heater (by the weekly program) for minimum 4  hours
starting from the scheduled start-up of disinfection. If the
anti-legionella heater is restricted during disinfection, this
function will NOT be successful and the applicable warning
AH will be generated.
INFORMATION
In case of error code AH and no interruption of the
disinfection function occurred due to domestic hot water
tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to
program the start-up of the disinfection function at least
4  hours later than the last expected large hot water
tapping. This start-up can be set by installer settings
(disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage
eco 3  hours before the scheduled start-up of the
disinfection function to preheat the tank.
To determine which DHW tank mode you are using (method 1)
Check the installer settings table filled in by the installer.
To determine which DHW tank mode you are using (method 2)
Prerequisite: User profile = Detailed.
1 Go to the DHW tank temperature home page (Tank).
2 Check which icons are displayed:
If... is displayed

Reheat mode

Scheduled mode

Scheduled + reheat mode
 
4.5.2
Reheat mode
In reheat mode ( ),the DHW  tank continuously heats up to the
temperature shown on the DHW  tank temperature home page
(example: 50°C).
T t
1
60°C
50°C
40°C
15°C
00:00
07:00
T
DHW tank temperature
t
t
Time
INFORMATION
There is a risk of space heating capacity shortage/comfort
problem (in case of frequent domestic hot water operation,
frequent and long space heating interruption will happen)
when selecting [6‑0D]=0 ([A.4.1] Domestic hot water
Type=Reheat only).
EHBH04~16CBV + EHVH04~16S18+26CBV
Daikin Altherma – Low temperature split
4P449972-1 – 2016.06
order
to
avoid
unsuccessful
Then the DHW tank mode =...
3
2
4
t
14:00
21:00
INFORMATION
When the DHW tank mode is reheat, the risk for capacity
shortage and comfort problem is significant. In case of
frequent reheat operation, space heating function is
regularly interrupted.
In reheat mode, you can do the following:
You can...
Read out the desired reheat temperature.
Adjust the reheat temperature.
Condition:
is displayed on the DHW tank
temperature home page.
Activate the DHW tank booster mode.
Program an anti-legionella heater allowance
schedule to restrict when the anti-legionella
heater can operate.
Example: Only allow the anti-legionella heater to
operate during the night.
(Only for field supplied domestic hot water
pump for secondary return)
Program a domestic hot water pump schedule
to determine when to turn ON and OFF the pump.
When turned ON, the pump runs and makes sure
hot water is instantly available at the tap. To save
energy, only turn ON the pump during periods of
the day when instant hot water is necessary.
See also:
"4.5.5 Using the DHW tank temperature home page" on page 12
"4.5.6 Using the DHW tank booster mode" on page 13
"4.7 Preset values and schedules" on page 16
4.5.3
Scheduled mode
In scheduled mode ( ), the DHW  tank produces hot water
corresponding to a schedule. The best time to allow the tank to
produce hot water is at night, because the space heating demand is
lower.
Example:
T t
1
2
60°C
50°C
40°C
15°C
00:00
07:00
T
DHW tank temperature
t
t
Time
▪ Initially, the DHW  tank temperature is the same as the
temperature of the domestic water entering the DHW  tank
(example: 15°C).
▪ At 00:00 the DHW tank is programmed to heat up the water to a
preset value (example: Storage comfort = 60°C).
▪ During the morning, you consume hot water and the DHW  tank
temperature decreases.
4 Operation
Location
DHW tank
temperature
home page
Menu structure
4
3
5
t
14:00
21:00
User reference guide
11