Multiple Rooms - Two Lwt Zones - Daikin Altherma ERGA06DAV3(A) Installer's Reference Manual

Low temperature split
Hide thumbs Also See for Altherma ERGA06DAV3(A):
Table of Contents

Advertisement

5 Application guidelines
Setting
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
Benefits
Compared with heat pump convectors for one room:
▪ Comfort. You can set the desired room temperature, including
schedules, for each room via the remote controller of the
heat pump convectors.
Combination: Under floor heating + Heat pump
convectors – Multiple rooms
Setup
A
B
M1
A
Main leaving water temperature zone
B
Room 1
C
Room 2
a
External room thermostat
b
Remote controller of the heat pump convectors
▪ For each room with heat  pump convectors: The heat  pump
convectors are directly connected to the indoor unit.
▪ For each room with under  floor heating: A shut-off valve (field
supply) is installed before the under floor heating. It prevents hot
water supply when the room has no heating demand.
▪ For each room with heat  pump convectors: The desired room
temperature is set via the remote controller of the heat  pump
convectors.
▪ For each room with under  floor heating: The desired room
temperature is set via the external room thermostat (wired or
wireless).
▪ The user interface connected to the indoor unit decides the space
operation mode. Mind that the operation mode on each external
room thermostat and remote controller of the heat  pump
convectors must be set to match the indoor unit.
INFORMATION
To increase comfort and performance, Daikin recommends
to install the valve kit option EKVKHPC on each heat pump
convector.
Configuration
Setting
Unit temperature control:
▪ #: [2.9]
▪ Code: [C-07]
Number of water temperature
zones:
▪ #: [4.4]
▪ Code: [7-02]
Installer reference guide
14
Value
0 (Single zone): Main
C
b
a
Value
0 (Leaving water): Unit operation
is decided based on the leaving
water temperature.
0 (Single zone): Main
5.2.3
Multiple rooms – Two LWT zones
If the heat emitters selected for each room are designed for different
leaving water temperatures, you can use different leaving water
temperature zones (maximum 2).
In this document:
▪ Main zone = Zone with the lowest design temperature
▪ Additional zone = Zone with the highest design temperature
CAUTION
When there is more than one leaving water zone, you must
ALWAYS install a mixing valve station in the main zone to
decrease (in heating) the leaving water temperature when
the additional zone has demand.
Typical example:
Room (zone)
Living room (main zone)
Bed rooms (additional zone)
Setup
d
A
Additional leaving water temperature zone
B
Room 1
C
Room 2
D
Main leaving water temperature zone
E
Room 3
a
Remote controller of the heat pump convectors
b
User interface used as room thermostat
c
Mixing valve station
d
Pressure regulating valve
INFORMATION
A pressure regulating valve should be implemented before
the mixing valve station. This is to guarantee the correct
water flow balance between the main leaving water
temperature zone and the additional leaving water
temperature zone in relation to the required capacity of
both water temperature zones.
▪ For the main zone:
▪ A mixing valve station is installed before the under floor heating.
▪ The pump of the mixing valve station is controlled by the ON/
OFF signal on the indoor unit (X2M/29 and X2M/21; normal
closed shut-off valve output).
▪ The room temperature is controlled by the user interface, which
is used as room thermostat (optional equipment EKRUDAS).
ERGA04~08DAV3(A) + EHVH04+08S23DAV
Heat emitters: Design
temperature
Under floor heating: 35°C
Heat pump convectors: 45°C
A
C
B
a
a
D
c
E
b
Daikin Altherma – Low temperature split
4P499573-1A – 2018.11