6. Evacuating System

6. Evacuating System
This procedure is carried out to ensure there is no remaining refrigerant or other gases (nitrogen, etc.) in the
repaired outdoor unit and tubing.
6-1. Evacuating Repaired Outdoor Unit
(1) Check that each service valve of the gas tubes, liquid tube, and balance tube in the outdoor unit are fully closed.
(2) Connect the manifold gauge valves to the high-pressure and low-pressure sensor outlets of the outdoor unit.
(Figs. 7-a, 7-b)
(3) Connect the manifold gauge valves to the vacuum pump.
* If the AP pin (CN24) on the outdoor control PCB have already been short-circuited, step (4) is not necessary.
(4) Turn off power to the repaired outdoor unit and short-circuit the AP pin (CN24) on the outdoor control PCB.
CAUTION
(5) Turn the power ON at the outdoor unit where vacuum will be applied. Then run the vacuum pump and continue
evacuation until the vacuum condition falls to less than –14.7 psig { -101 kPa, 5 Torr }.
CAUTION
Vacuum pump
Vacuum pump
6-2. Evacuating Refrigerant Tubing Between Indoor and Outdoor Units
Refer to the "Installation Instructions" that came with the outdoor unit.
By short-circuiting the AP pin (CN24) and turning on power to the outdoor unit, all
electronic valves in the outdoor unit are forcibly opened and any remaining nitrogen
gas can be recovered. Failure to perform this procedure may result in nitrogen
gas remaining in the refrigerant circuit and causing operating problems. Therefore,
never skip this step.
To ensure proper evacuation, refer to the operating instructions that came with the
vacuum pump.
Type: 72, 96
Manifold
gauge
Lo
Hi
Type: 120, 144
Manifold
gauge
Lo
Hi
2 - 15
2WAY VRF SYSTEM
2WAY VRF SYSTEM
Outdoor Unit Repair Procedures
Outdoor Unit Repair Procedures
Low-pressure outlet port
(for ø5/16" (ø7.94mm)-dia connector)
High-pressure outlet port
(for ø5/16" (ø7.94mm)-dia connector)
Liquid tube service port
(for ø5/16" (ø7.94mm)-dia connector)
Gas tube service port
(for ø5/16" (ø7.94mm)-dia connector)
Low-pressure outlet port
(for ø5/16" (ø7.94mm)-dia connector)
High-pressure outlet port
(for ø5/16" (ø7.94mm)-dia connector)
Liquid tube service port
(for ø5/16" (ø7.94mm)-dia connector)
Gas tube service port
(for ø5/16" (ø7.94mm)-dia connector)
1
2
3
4
5
Fig. 7-a
6
7
8
Fig. 7-b