Panasonic U-120ME2U9 Service Manual page 124

Table of Contents

Advertisement

2. Detailed Settings Function
Item code
Automatic drain pump
Ventilation fan operation
Wired remote controller
Temperature display
"Operation change
1
control in progress"
OFF reminder function
for when weekly timer is
Humidifier / emergency
2
heater output setting
Discharge temperature
Heat exchanger
temperature for cold air
3
(Heat exchanger control
point for control to
prevent cold air)
Fan output switching
4
Drain pump delayed
5
Humidifier setting
6
Flap operation mode
Flap swing mode
7
8
9
Item
No.
0000
No forced operation
0001
Forced operation for 1 minute
operation
0060
Continuous operation
0000
None
0001
Ventilation fan operated by remote controller.
0000
Not used. (Body sensor is used.)
sensor
0001
Remote control sensor is used.
0000
°C
setting
0001
°F
0000
Normal (displayed)
0001
Not displayed
display
0000
None
0001
Only stop time setting is enabled.
used
0000
Humidifier output
0002
Emergency heater output
0000
Discharge temperature control OFF
control
0001
Discharge temperature control ON
0013
Control temperature 55°F
0014
Control temperature 57°F
discharge
0025
Control temperature 77°F
0026
Control temperature 78°F
0000
Output linked with fan. (ON when indoor unit fan is operating.)
0001
Fan mode operation output
0000
No delayed stop
0001
1 sec. delayed stop
0002
2 sec. delayed stop
stop time
0058
58 sec. delayed stop
0059
59 sec. delayed stop
0060
60 sec. delayed stop
0000
Humidifier output OFF. Drain pump stopped.
0001
Humidifier output ON. Drain pump operates.
Humidifier output ON. Drain pump operates for 1 minute when total humidifier
0002
operating time reaches 60 minutes.
0003
Humidifier output ON. Drain pump stopped.
0000
Standard setting
0001
Draft reduction mode (Flap lower-limit position is shifted upwards.)
0000
Smudging reduction mode (Flap swing upper-limit position is shifted downwards.)
0001
Normal mode
0002
Draft reduction mode (Flap swing lower-limit position is upwards.)
Setting data
Description
1 min. delayed stop
2 min. delayed stop
Except
Indoor unit
Type
58 min. delayed stop
F2, U2, T2
59 min. delayed stop
60 min. delayed stop
4 - 12
2WAY VRF SYSTEM
Remote Controller Functions
Indoor unit
Type
F2, U2, T2