Panasonic WH-WDG05LE5 Installation Manual
Panasonic WH-WDG05LE5 Installation Manual

Panasonic WH-WDG05LE5 Installation Manual

Air-to-water heatpump outdoor unit
Hide thumbs Also See for WH-WDG05LE5:

Advertisement

Quick Links

Installation Manual
AIR-TO-WATER HEATPUMP OUTDOOR UNIT
WH-WDG05LE5, WH-WDG07LE5,
WH-WDG09LE5
CAUTION
R290
REFRIGERANT
This AIR-TO-WATER HEATPUMP contains
and operates with refrigerant R290.
THIS PRODUCT MUST ONLY BE INSTALLED OR SERVICED
BY QUALIFIED PERSONNEL.
Refer to National, State, Territory and local legislation,
regulations, codes, installation & operation manuals, before
the installation, maintenance and/or service of this product.
SAFETY PRECAUTIONS
• Read the following "SAFETY PRECAUTIONS" carefully before installation.
• Electrical work and water installation works must be done by licensed electrician and licensed water system installer respectively. Be sure
to use the correct rating and main circuit for the model to be installed.
• The caution items stated here must be followed because these important contents are related to safety. The meaning of each indication
used is as below. Incorrect installation due to ignoring or negligence of the instruction will cause harm or damage, and the seriousness is
classifi ed by the following indications.
• Please leave the installation manual with the unit after installation.
WARNING
CAUTION
The items to be followed are classifi ed by the symbols:
• Carry out test running to confi rm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
• This appliance is not intended for accessibility by the general public.
• If there is any doubt about the installation procedure or operation, always contact the authorized dealer for advice and information.
Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer. Any unfi t method or
using incompatible material may cause product damage, burst and serious injury.
Do not install outdoor unit near handrail of veranda. When installing outdoor unit at veranda of high rise building, child may climb up to outdoor
unit and cross over the handrail and causing accident.
Do not use unspecifi ed cord, modifi ed cord, joint cord or extension cord for power supply cord. Do not share the single outlet with other electrical
appliances. Poor contact, poor insulation or over current will cause electrical shock or fi re.
Do not tie up the power supply cord into a bundle by band. Abnormal temperature rise on power supply cord may happen.
WEB-ACXF60-51540-EN
This indication shows the possibility of causing death or serious injury.
This indication shows the possibility of causing injury or damage to properties only.
Symbol with white background denotes item that is PROHIBITED.
Symbol with dark background denotes item that must be carried out.
Required tools for Installation Works
1
Phillips screw driver
2
Level gauge
3
Electric drill, hole core drill
4
Hexagonal wrench
(4 mm)
5
Spanner
6
Pipe cutter
7
Reamer
8
Knife
9
Gas leak detector
10 Measuring tape
11 Thermometer
12 Megameter
Explanation of symbols displayed on the indoor unit or outdoor unit.
WARNING
CAUTION
CAUTION
CAUTION
WARNING
ENGLISH
13 Multimeter
14 Torque wrench
18 N•m (1.8 kgf•m)
42 N•m (4.3 kgf•m)
55 N•m (5.6 kgf•m)
65 N•m (6.6 kgf•m)
100 N•m (10.2 kgf•m)
15 Hand gloves
(for refrigerant circuit repair
16 Vacuum pump
17 Gauge manifold
18 Recovery machine
19 Recovery cylinder)
This symbol shows that this equipment uses
a fl ammable refrigerant with safety A3 group
per ISO 817. If the refrigerant is leaked,
together with an external ignition source,
there is a possibility of fi re/explosion.
This symbol shows that the Installation
Manual should be read carefully.
This symbol shows that a service personnel
should be handling this equipment with
reference to the Installation Manual.
This symbol shows that there is information
included in the Operation Manual and/or
Installation Manual.
1

Advertisement

loading

Summary of Contents for Panasonic WH-WDG05LE5

  • Page 1 ENGLISH Installation Manual AIR-TO-WATER HEATPUMP OUTDOOR UNIT WH-WDG05LE5, WH-WDG07LE5, WH-WDG09LE5 Required tools for Installation Works Phillips screw driver 13 Multimeter CAUTION Level gauge 14 Torque wrench Electric drill, hole core drill 18 N•m (1.8 kgf•m) 42 N•m (4.3 kgf•m) Hexagonal wrench 55 N•m (5.6 kgf•m)
  • Page 2 Do not insert your fi ngers or other objects into the unit, high speed rotating fan may cause injury. Do not sit or step on the unit, you may fall down accidentally. Keep plastic bag (packaging material) away from small children, it may cling to nose and mouth and prevent breathing. Do not purchase unauthorized electrical parts for installation, service, maintenance and etc..
  • Page 3 PRECAUTION FOR USING R290 REFRIGERANT • pay careful attention to the following points: WARNING The mixing of different refrigerants within a system is prohibited. Operation, maintenance, repairing and refrigerant recovery should be carried out by trained and certifi ed personnel in the use of fl ammable refrigerants and as recommended by the manufacturer.
  • Page 4 2-4. Presence of fi re extinguisher • If any hot work is to be conducted on the refrigerating equipment or any associated parts, appropriate fi re extinguishing equipment shall be available at hand. • Have a dry powder or CO fi...
  • Page 5 7. The following leak detection methods are deemed acceptable for all refrigerant systems. • No leaks shall be detected when using detection equipment with a sensitivity of 5 grams per year of refrigerant or better under a pressure of at least 0,25 times the maximum allowable pressure (>0.98MPa, max 3.90MPa).
  • Page 6 12. Recovery • When removing refrigerant from a system, either for servicing or decommissioning, it is recommended good practice that all refrigerants are removed safely. • When transferring refrigerant into cylinders, ensure that only appropriate refrigerant recovery cylinders are employed. •...
  • Page 7: Select The Best Location

     If an awning is built over the unit to prevent direct sunlight or rain, be careful that heat radiation from the condenser is not obstructed.  For WH-WDG05LE5, WDG07LE5 and WDG09LE5, avoid installations in areas where the ambient temperature may drop below-25°C.
  • Page 8 INSTALL THE OUTDOOR UNIT DIMENSION DIAGRAM It is advisable to avoid more than 2 blockage directions. For better ventilation & multiple-outdoor installation, please consult authorized dealer/specialist. Top view Front view Side view Rear view (160) Water outlet port Pressure relief valve connecting port Drain hole Connecting cable...
  • Page 9: Connect The Cable To The Outdoor Unit

    CONNECT THE CABLE TO THE OUTDOOR UNIT (FOR DETAIL REFER TO WIRING DIAGRAM AT UNIT) 1. Attach the discharge grille (left side) 3 for safety before connecting the cable. Screw 5 in 4 places 4 claw hooks 2. Connecting cable between indoor unit and outdoor unit shall be approved polychloroprene sheathed fl exible cable (see below table), type designation 60245 IEC 57 or heavier cable.
  • Page 10: Pipe Insulation

    WARNING This equipment must be Screw properly earthed. Terminals on the indoor unit Colour of wires Earth Wire Terminals on the outdoor unit must be longer than other wires for safety Tightening torque reason. Terminal screw cN•m {kgf•cm} Cable gland 157 ~ 196 {16 ~ 20} 196 ~ 245 {20 ~ 25} WIRE STRIPPING AND CONNECTING REQUIREMENT...