Water Heat Exchanger Unit
(1) The operating ranges for both cooling and heating are the same as for Multi systems for
buildings.
(2) Water heat exchanger temperature range
Cooling temperature range: 5 to 15°C
Heating temperature range: 35 to 55°C
(3) Water heat exchanger unit connection limitations
Item
Allowable
pipe length
Allowable
difference in height
* For cooling operation where the outdoor air temperature is 10ºC or less, this value should be 30m.
GHP Chiller TECHNICAL DATA.indb A-3
GHP Chiller TECHNICAL DATA.indb A-3
Para-meter
Parameter description
L
Maximum allowable pipe length
1
If outdoor unit is higher
H
1
If outdoor unit is lower
A-3
2. System characteristics
Actual length (m)
≤170 (equivalent length 200)
≤50
≤35*
2012/04/06 13:41:59
2012/04/06 13:41:59