TX90 6kVA & 10kVA User's Manual
10 kVA tower Output No.
No.1 (L21-N21)
No.2 (L22-N22)
No.3 (L23-N22)
No.4 (L21-N22)
• CAUTION: To reduce the risk of fire connect the UPS input to a circuit provided with branch circuit over-
current protection for 40A for 6kVA and 60A for 10kVA rating in accordance with the National Electric
Code, ANSI/NFPA 70.
• Install the UPS so that it is not likely to be contacted by people.
• The maximum ambient operating temperature is 40°C or equivalent.
• Units are considered acceptable for use in a maximum ambient 40°C.
• Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and
the required precautions.
• When replacing batteries, replace with the same type and number of batteries or battery packs.
• CAUTION – Risk of fire hazard, UPS can be used with four Battery Cabinets.
• CAUTION - RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN INCORRECT TYPE. DISPOSE OF USED BAT-
TERIES ACCORDING TO THE INSTRUCTIONS.
• CAUTION - Do not dispose of batteries in a fire. The batteries may explode.
• CAUTION – Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It may
be toxic.
• CAUTION– A battery can present a risk of electrical shock and high short circuit current. The following
precautions should be observed when working on batteries:
1. Remove watches, rings, or other metal objects.
2. Use tools with insulated handles.
3. Wear rubber gloves and boots.
4. Do not lay tools or metal parts on top of batteries.
5. Disconnect charging source prior to connecting or disconnecting battery terminals.
6. Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from
ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood
of such shock can be reduced if such grounds are removed during installation and maintenance
(applicable to equipment and remote battery supplies not having a grounded supply circuit).

Battery Care

If the UPS is unused for an extended period of time it must be stored in a moderate climate. The batteries should
be charged for twelve hours every three months by plugging the UPS power cord into a wall receptacle and turn-
ing on the input breaker on the front panel. Repeat this procedure every two months under a high-temperature
environment.
Xtreme Power Conversion Corporation
Output rating
6 kVA, 120 V
6 kVA, 120 V
10 kVA, 208 V
10 kVA, 240 V
Uninterruptible Power Supply
Ratings of output branch circuit
over-current protection
45
45
50
45
Page 5