Safety Instructions And Battery Care

Safety Instructions

• For Parallel System installation please refer to TX90 6kVA & 10kVA Parallel System Installation Guide
• Due to small leakage currents generated by the EMI filter in the UPS it is necessary to double check that
the ground wire of the UPS is properly grounded before connecting the UPS to the AC mains.
• To ensure safety in all applications where a UPS is hard wired to the electrical supply, ensure that the sys-
tem is installed by a qualified electrical contractor.
• The UPS has its own internal energy source (battery). Should the battery be switched on when no AC
power is available there could be voltage at the output terminals.
• Make sure that the AC utility outlet is correctly grounded.
• Do not open the case as there are no serviceable parts inside. Opening the case voids the warranty.
• Do not try to repair the unit yourself; contact your local supplier. Repairing the unit yourself voids the war-
ranty.
• Please make sure that the input voltage of the UPS matches the supply voltage.
• Use a certified input power cable with the correct plugs and sockets for the appropriate system voltage.
• To prevent any overheating of the UPS keep all ventilation openings free from obstruction, and do not
store things on top of the UPS. Keep the UPS 30 cm away from the wall.
• Ensure that the UPS is installed within the proper environmental range. (0-40°C and 0-90% non-condens-
ing humidity)
• Do not install the UPS in direct sunlight. Your warranty may be void if the batteries fail.
• Install the UPS indoors as it is not designed for installation outdoors.
• Dusty, corrosive and salty environments can damage any UPS.
• Install the UPS away from objects that give off excessive heat and areas that are excessively wet.
• If liquids are spilled onto the UPS or foreign objects dropped into the unit the warranty will be null and
void.
• The battery will discharge naturally if the system is unused for a long period of time.
• The UPS should be recharged every 2-3 months if unused. If this is not done then the warranty will be
null and void. When installed and being used the batteries will be automatically recharged and kept in top
condition.
• Do not install the UPS in an environment with sparks, smoke or hazardous gas.
• Make sure the UPS is completely turned off when transporting it. It might cause electrical shock if the
output is not cut completely.
• The UPS includes a Maintenance Bypass Switch. Please follow the procedures strictly when switching on
or off the Maintenance Bypass Switch.
• The UPS offers a CVCF (Constant Voltage Constant Frequency) setting function.
1. For correct setting and wiring please contact with your local utility agent.
2. Do not set it yourself or your warranty will be void.
• This UPS has been designed and constructed to protect your assets from the wide range of power aberra-
tions experienced on utility power lines today. It is your insurance for a reliable, clean and stable voltage
supply. It is worth taking care to install the system correctly and to have it maintained correctly by your
local dealer.
• SAVE THESE INSTRUCTIONS. This manual contains important instructions that should be followed during
installation and maintenance of the UPS and batteries.
• The UPS is intended for installation in a controlled environment.
• CAUTION: A disconnect switch must be provided by others for the AC output circuit. To reduce the risk of
fire connect only to a circuit provided with branch circuit over-current protection for 30 amperes for 6kVA
(See below for 10 kVA details) rating in accordance with the National Electric Code, ANSI/NFPA 70.